11) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to Chapter 8-4. "Details of function" on page 18
Function
number
Setting value Setting description
Factory
setting
61
00 Auxiliary heater control 1 ♦
01 Auxiliary heater control 2
02 Heat pump prohibition control
03 Auxiliary heater control by outdoor temperature 1
04 Auxiliary heater control by outdoor temperature 2
12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to Chapter 8-4. "Details of function" on page 18.
Function
number
Setting
value
Setting description
Factory
setting
Setting value of function 61:
00 and 01
Setting value of function 61:
02 to 04
Heater: On Heater: Off Heater: On Heater: Off
62
00 -3 °C -1 °C -0.5 °C 0.5 °C ♦
01 -2 °C -1 °C -1 °C 0.5 °C
02 -2 °C -1 °C -2 °C 0.5 °C
03 -3 °C -1 °C -3 °C 0.5 °C
04 -4 °C -1 °C -4 °C 0.5 °C
05 -5 °C -1 °C -5 °C 0.5 °C
13) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to Chapter 8-4. "Details of function" on page 18.
Function number Setting value Setting description Factory setting
66
00 -20 °C ♦
01 -18 °C
02 -16 °C
03 -14 °C
04 -12 °C
05 -10 °C
06 -8 °C
07 -6 °C
08 -4 °C
- 39 -
11-1. Function settings by using remote controller 11. Function settings
WALL MOUNTED
ASTG09-12KMTC
WALL MOUNTED
ASTG09-12KMTC