EasyManua.ls Logo

Fujitsu ASU7RLF - Service Manual

Fujitsu ASU7RLF
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
INVERTER MULTI
AIR CONDITIONER
CONTENTS
SPECIFICATIONS . . . . . . . . . . . . . . . . . . .
1
DIMENSIONS. . . . . . . . . . . . . . . . . . . . . . .
7
REFRIGERANT SYSTEM DIAGRAM . . .
13
ERROR DETECTION. . . . . . . . . . . . . . . .
36
CIRCUIT DIAGRAM . . . . . . . . . . . . . . . . .
14
INDOOR PCB CIRCUIT DIAGRAM. . . . .
19
OUTDOOR PCB CIRCUIT DIAGRAM . . .
22
PARTS (INDOOR UNIT) . . . . . . . . . . . . .
38
PARTS (OUTDOOR UNIT) . . . . . . . . . . .
42
ACCESSORIES. . . . . . . . . . . . . . . . . . . .
61
Indoor unitOutdoor unit
ASU7RLF
ASU9RLF
ASU12RLF
ASU18RLF
AUU9RLF
AUU12RLF
AUU18RLF
UTG-CCGF
ARU9RLF
ARU12RLF
ARU18RLF
AOU24RLXFZ

Other manuals for Fujitsu ASU7RLF

Questions and Answers

  • P
    Philip TownsendAug 13, 2025
    What to do if my Fujitsu ASU7RLF Air Conditioner remote is not working due to a communication error?
    • A
      Adam AyalaAug 14, 2025
      If you're experiencing a Wired Remote Controller Communication Error with your Fujitsu Air Conditioner, check the voltage. If it's DC12V, the remote control has failed and should be replaced. If it's DC 0V, the Controller PCB has failed and should be replaced after rechecking the remote control.
  • W
    Walter GoldenAug 17, 2025
    What to do if my Fujitsu Air Conditioner has a drainage error?
    • A
      Alisha KingAug 17, 2025
      If your Fujitsu Air Conditioner is experiencing drainage issues, start by inspecting the float switch for proper operation using a meter to check its on/off switching. If the float switch is defective, replace it. Also, examine the drain hose for any clogs and clear them if necessary. If these steps don't resolve the issue, consider replacing the controller PCB.
  • P
    powelledwardAug 21, 2025
    How to fix a Fujitsu ASU7RLF Air Conditioner indoor unit fan motor error?
    • T
      Thomas AllenAug 21, 2025
      If you're encountering an indoor unit fan motor error with your Fujitsu Air Conditioner, check first the fan and bearing. If either is damaged, replace them. If the motor itself is faulty, replace the indoor unit fan motor. If these steps do not resolve the issue, replace the controller PCB.
  • B
    Brandon FrancisAug 25, 2025
    What to do if my Fujitsu ASU7RLF Air Conditioner shows an indoor room thermistor error?
    • J
      John MorganAug 25, 2025
      If your Fujitsu Air Conditioner displays an indoor room thermistor error, begin by checking the connector to ensure it is securely attached and properly connected, and verify that the thermistor cable is not open. If the thermistor is either open or shorted, replace it and then reset the power.
  • A
    Adrian HaynesAug 29, 2025
    How to troubleshoot an Indoor Unit Model Information Error on my Fujitsu ASU7RLF?
    • J
      Jeffrey SnyderAug 29, 2025
      If your Fujitsu Air Conditioner is showing an Indoor Unit Model Information Error, check for external causes such as noise and ensure the ground connection is properly connected. Also, inspect all connectors for looseness or incorrect wiring, and check the PCB for any shorts or corrosion. If the problem persists, consider replacing the Controller PCB.
  • R
    Roy BranchSep 1, 2025
    What does an Indoor Unit Capacity Error mean on my Fujitsu ASU7RLF Air Conditioner?
    • C
      Cynthia FergusonSep 1, 2025
      If your Fujitsu Air Conditioner is showing an Indoor Unit Capacity Error, first verify the total capacity of the connected indoor units. If an abnormal condition is found, correct it by referring to the Installation Manual or Design & Technical Manual. If the problem persists, replace the Main PCB of the Outdoor unit.
  • B
    Brian CarterSep 4, 2025
    How to fix a Serial Communication Error (Serial Reverse Transfer Error) on a Fujitsu Air Conditioner?
    • K
      Kimberly WilsonSep 4, 2025
      If your Fujitsu Air Conditioner displays a Serial Communication Error (Serial Reverse Transfer Error), check all connection lines between the indoor and outdoor units for any looseness or disconnections, referring to the Installation Manual or Data & Technical Manual for correction. Also, check the voltage of the power supply, ensuring it appears at the outdoor unit terminal L1 - L2 within the range of AC187V - 253V. Check that the indicated value swings between AC90V and AC270V at outdoor unit terminal 1 - 3. If the outdoor fan motor, active filter module, or IPM is abnormal, replace the corresponding part. If all parts are normal, replace the Main PCB.
  • R
    Raven JacksonSep 9, 2025
    How to resolve a Damper (Open/Close) simultaneous detection Limit switch error on a Fujitsu ASU7RLF Air Conditioner?
    • C
      Carla RamirezSep 9, 2025
      If your Fujitsu Air Conditioner displays a Damper(Open/Close) simultaneous detection Limit switch error, replace the limit switch if it is defective. If the problem persists, replace the Controller PCB.

Summary

SPECIFICATIONS

OUTDOOR UNIT SPECIFICATIONS

Electrical, compressor, refrigerant, and measurement data for the outdoor unit.

INDOOR UNIT COMPACT WALL MOUNTED SPECIFICATIONS

Electrical, fan motor, air flow, and noise level specs for ASU/ARU models.

INDOOR UNIT WALL MOUNTED ASU18 RLF SPECIFICATIONS

Electrical, fan motor, noise, and measurement data for ASU18RLF.

INDOOR UNIT COMPACT CASSETTE SPECIFICATIONS

Electrical, fan motor, air flow, noise, and measurement specs for AUU models.

INDOOR UNIT SLIM DUCT SPECIFICATIONS

Electrical, fan motor, air flow, noise, and measurement specs for ARU slim duct models.

OUTDOOR UNIT DIMENSIONS

INDOOR UNIT COMPACT WALL MOUNTED DIMENSIONS

INDOOR UNIT WALL MOUNTED ASU18 RLF DIMENSIONS

INDOOR UNIT COMPACT CASSETTE DIMENSIONS

INDOOR UNIT SLIM DUCT DIMENSIONS

REFRIGERANT SYSTEM DIAGRAM

OUTDOOR UNIT CIRCUIT DIAGRAM

INDOOR UNIT COMPACT WALL MOUNTED CIRCUIT DIAGRAM

INDOOR UNIT WALL MOUNTED ASU18 RLF CIRCUIT DIAGRAM

INDOOR UNIT COMPACT CASSETTE CIRCUIT DIAGRAM

INDOOR UNIT SLIM DUCT CIRCUIT DIAGRAM

OUTDOOR PCB CIRCUIT DIAGRAM

INDOOR PCB CIRCUIT DIAGRAM COMPACT WALL MOUNTED

INDOOR UNIT COMPACT WALL MOUNTED CONTROLLER PCB ASSEMBLY

INDOOR UNIT COMPACT CASSETTE CONTROL UNIT CIRCUIT DIAGRAM

INDOOR UNIT SLIM DUCT CONTROL UNIT CIRCUIT DIAGRAM

OUTDOOR UNIT ERROR DETECTION

INDOOR UNIT AND REMOTE CONTROL ERROR CODES

SIMPLE REMOTE CONTROL ERROR DISPLAY

How simple remote controls display errors and recommended action.

WIRED REMOTE CONTROL ERROR DISPLAY

Error display on wired remote controls and immediate contact advice.

OUTDOOR UNIT PARTS

INDOOR UNIT COMPACT WALL MOUNTED PARTS

INDOOR UNIT WALL MOUNTED ASU18 RLF PARTS

DECORATION PANEL UTG-CCGF PARTS

INDOOR UNIT COMPACT CASSETTE PARTS

INDOOR UNIT COMPACT CASSETTE CONTROL UNIT PARTS

INDOOR UNIT SLIM DUCT PARTS

INDOOR UNIT SLIM DUCT ARU18 RLF PARTS

OUTDOOR UNIT ACCESSORIES

INDOOR UNIT COMPACT WALL MOUNTED ACCESSORIES

INDOOR UNIT WALL MOUNTED ACCESSORIES

List of accessories for compact wall-mounted and ASU18RLF indoor units.

INDOOR UNIT COMPACT CASSETTE ACCESSORIES

DECORATION PANEL UTG-CCGF ACCESSORIES

List of parts and accessories for compact cassette indoor units and decoration panel.

INDOOR UNIT COMPACT CASSETTE ACCESSORIES

INDOOR UNIT SLIM DUCT ACCESSORIES

Fujitsu ASU7RLF Specifications

General IconGeneral
BrandFujitsu
ModelASU7RLF
CategoryAir Conditioner
LanguageEnglish