1-4. Rotation number of compressor at normal start-up
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Frequency VI
Time 1
Time 2 Time 3
Time 4
Time 5
Time 6
Frequency (rps)
I II III IV V VI
35 52 64 71 89 97
Time (sec)
1 2 3 4 5 6
60 140 170 200 350 410
1-4. Rotation number of compressor at normal start-up - (04-4) - 1. Rotation number control of compressor