8. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the table 10.
Cooling Heating
Min Max Min Max Min Max
Dry
AS*A07/ 09LGC
AS*A12LGC
22Hz 79Hz 22Hz 99Hz 28Hz 37Hz
18Hz 96Hz 18Hz 130Hz 25Hz 33Hz
AS*A14LGC 18Hz 80Hz 18Hz 101Hz 20Hz 27Hz
AS*A07/ 09LGC
AS*A12LGC
70Hz 82Hz 92Hz 96Hz 96Hz 96Hz
56Hz 74Hz 87Hz 97Hz 108Hz 119Hz
AS*A14LGC
40Hz 59Hz 72Hz 85Hz 101Hz 110Hz
80sec 60sec 60sec 180sec 60sec 60sec
80sec 60sec 60sec 180sec 60sec 60sec
(Table 10 : Compressor Operation Frequency Range)
2. OPEARTION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the figure 10.
(Fig.10 : Compressor Control at Start-up)
Time
Time Time Time
Time
Time
(Frequency)
(Time)
Frequency
Frequency
Frequency Frequency
Frequency
Frequency
Time Time
Time Time Time Time
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
05-09
AS*A07/ 09LGC
AS*A12LGC
120sec 60sec 40sec 50sec 80sec 60sec
AS*A14LGC