1-5. Limitation of compressor rotation number by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Model name Outdoor temperature zone
Limitation of compressor
rotation number
AOYG07KMCC
AOYG09KMCC
AOYG12KMCC
A zone 42 rps
B zone 42 rps
C zone 33 rps
D zone 28 rps
E zone 16 rps
F zone 21 rps
AOYG14KMCC
A zone 36 rps
B zone 36 rps
C zone 28 rps
D zone 26 rps
E zone 1 rps
F zone 36 rps
1-5. Limitation of compressor rotation number by outdoor temperature - (04-6) - 1. Rotation number control of compressor