6) Static pressure
Select the appropriate static pressure according to the installation conditions.
For mini duct type:
Function number Setting value Setting description Factory setting
26
00 0 Pa
01 10 Pa
02 20 Pa
03 30 Pa
04 40 Pa
05 50 Pa
31
Standard
(10 Pa: 07, 09, 12 type)
(15 Pa: 14, 18 type)
NOTES:
Range of static pressure is different by model.
Model name Range of static pressure
07 type
0 to 30 Pa09 type
12 type
14 type
0 to 50 Pa
18 type
Setting number in 07, 09, or 12 type is “04 to 30”: Operation is same as that “03”.
Setting number in 14 or 18 type is “06 to 30”: Operation is same as that “05”.
Setting number value cannot be set to 32 or more.
For slim duct type:
Function number Setting value Setting description Factory setting
26
00 0 Pa
01 10 Pa
02 20 Pa
03 30 Pa
04 40 Pa
05 50 Pa
06 60 Pa
07 70 Pa
08 80 Pa
09 90 Pa
31 Standard (25 Pa)
DESIGN & TECHNICAL MANUAL
- 244 -
MULTI TYPE
5, 6 ROOMS TYPE

Table of Contents

Other manuals for Fujitsu asyg18lfca

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu asyg18lfca and is the answer not in the manual?

Fujitsu asyg18lfca Specifications

General IconGeneral
BrandFujitsu
Modelasyg18lfca
CategoryAir Conditioner
LanguageEnglish

Related product manuals