Fujitsu Eternus DX90 S2 - Figure 1.24 Power Distribution Unit (AC200-240 V, 2 U, Max 6 Enclosures Connection); Table 1.8 Power Distribution Unit (AC200-240 V, 1 U, Max 2 Enclosures Connection) and Provided AC Cable Specifications; Table 1.9 Power Distribution Unit (AC200-240 V, 2 U, Max 6 Enclosures Connection) and Provided AC Cable Specifications

Fujitsu Eternus DX90 S2
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1 Hardware Configurations
1.5 Power Distribution Units (Only for Regions Other than EMEA&I)
ETERNUS DX80 S2/DX90 S2 Disk storage system User’s Guide -Site Planning-
Copyright 2013 FUJITSU LIMITED P3AM-4822-12ENZ0
25
The following table shows the specifications of a power distribution unit and the AC cables that are provided.
Table 1.8 Power distribution unit (AC200-240V, 1U, Max 2 enclosures connection) and provided AC cable
specifications
â–  Power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 6 enclosures
connection)
There are 12 outlets.
Figure 1.24 Power distribution unit (AC200-240V, 2U, Max 6 enclosures connection)
The following table shows the specifications of a power distribution unit and the AC cables that are provided.
Table 1.9 Power distribution unit (AC200-240V, 2U, Max 6 enclosures connection) and provided AC cable
specifications
Item Specifications
Power Voltage AC200 - 240V
Phase Single
Frequency 50Hz/60Hz
Input cable Connection type IEC60320-C13 ↔ NEMA L6-15P
Length 4m
Quantity 2
Output cable Connection type IEC60320-C13 ↔ IEC60320-C14
Length 3m
Quantity 4
Item Specifications
Power Voltage AC200 - 240V
Phase Single
Frequency 50Hz/60Hz
Input cable Connection type Straight-through ↔ NEMA L6-20P
Length 4m
Quantity 2
Output cable Connection type IEC60320-C13 ↔ IEC60320-C14
Length 3m
Quantity 12
Outlets (OUTPUT)