Inverter Error
YES
NO
OK
Check Point 1-2 : Noise, momentary open, voltage drop
Inverter PCB
Error information received from Inverter PCB
1. Noise, momentary open, voltage drop. 2. Power supply to Inverter PCB
wiring disconnection, open 3. Inverter PCB defective
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the
power line.
Check Point 2 : Check the wiring (Power supply to Inverter PCB)
Connector and wiring connection state check
Cable open check
Check Inverter PCB.
(Refer to Parts information 3, 4)
Check Point 1-1 : Turn the power
on again.
Error displayed again?
Check Point 3 : Check Inverter PCB
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 63. 1
Error Code : 63
Trouble shooting 37
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
E. 63.1
04-45

Table of Contents

Other manuals for Fujitsu UTP-VX90A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTP-VX90A and is the answer not in the manual?

Fujitsu UTP-VX90A Specifications

General IconGeneral
BrandFujitsu
ModelUTP-VX90A
CategoryAir Conditioner
LanguageEnglish

Related product manuals