Function
Function
number
Setting number Default Details
Filter
indicator
interval
11
00 Standard
Adjust the filter cleaning interval notification. If the notification is too
early, change to setting 01. If the notification is too late, change to
setting 02.
01 Longer
02 Shorter
Filter
indicator
action
13
00 Enable
Enable or disable the filter
indicator. Setting 02 is for use
with a central remote control.
01 Disable
02
Display only on
central remote
control
Static pressure 26
05 SP mode 05
Model name
Range of static
pressure
Normal static
pressure
ARXH054GTAH
SP mode 05 to 19
(50 to 185 Pa)
185Pa
ARXH072GTAH
SP mode 05 to 20
(50 to 200 Pa)
200Pa
ARXH096GTAH
SP mode 05 to 22
(50 to 220 Pa)
200Pa
06 SP mode 06
07 SP mode 07
08 SP mode 08
09 SP mode 09
10 SP mode 10
11 SP mode 11
12 SP mode 12
13 SP mode 13
14 SP mode 14
15 SP mode 15
16 SP mode 16
17 SP mode 17
18 SP mode 18
19 SP mode 19
20 SP mode 20
21 SP mode 21
22 SP mode 22
31 Normal SP
*1 Auto
restart
40
00 Enable
Enable or disable automatic system restart after a power outage.
01 Disable
Cool Air
Prevention
43
00 Prohibited
Setting change prohibited.
01
Follow the setting
on the remote
controller
External
control
46
00 Start/Stop
Allow an external controller to start or stop the system, or to perform
an emergency stop, or to perform a forced stop.
* If an emergency stop is performed from an external controller, same
refrigerant system will be disabled.
* If forced stop is set,indoor unit stops by the input to the external input
terminals,and Start/Stop by a remote controller is restricted.
01 Emergency stop
02 Forced stop
Error
report
target
47
00 All
Change the target for reporting errors. Errors can either be reported in
all locations, or only on the wired remote.
01
Display only on
central remote
control
Humidifier
contro
l
63
00 mode 00
Select control conditions of external output.
"Mode 00" is output when heating thermostat is ON, "Mode 01" is
output in heating operation, "Mode 02" is output in heating operation
and in fan operation.
01 mode 01
02 mode 02
1-6 FIELD SETTING / FUNCTION SETTING FOR OUTDOOR AIR UNIT
01-21