02-06
Capacity priority setting
Operation mode
Low noise level setting
ON
OFF
520
8
ON
ON
COOL
HEAT
«
Low noise mode and operation contents
»
( PUSH SW ) ( PUSH SW )
Normal operation
Low
capacity
Not switched for 30 minutes
after being once switched.
* Automatic switching
«
Settings and corresponding operations
»
LOW NOISE MODE
* Automatic switching
* Low capacity
Compressor capacity is low
or
High-pressure is high (high-pressure saturation 58°C) at cooling
or
Low-pressure is low (low-pressure saturation 0°C) at heating
Operation in low noise mode
When the low noise mode setting ON from PUSH SW or EXTERNAL INPUT, the outdoor unit operates in
the low noise mode as follows.
LOW NOISE MODE
The operating sound lowers from about 3 to 5 dB more than the rated value
Capacity does not become low
even when switched to low noise
mode
The operating noise is reduced by limiting the rotational speed of the compressor and fan motor
2-3-3
Low noise mode
400
48
590
9
510
63
700
10
620
80
520
8
400
55
590
9
510
65
700
10
620
85
Max FAN Step
Max FAN Step
Max Compressor Speed
Max Compressor Speed
Upper FAN
Lower FAN
Upper FAN
Lower FAN
L
Level 1
ow Noise Mode
AJ*072LELAH
AJ*090LELAH AJ*108LELAH
440
7
COOL
HEAT
330
35
520
8
400
47
520
8
400
54
440
7
330
37
520
8
400
48
520
8
400
58
Max FAN Step
Max FAN Step
Max Compressor Speed
Max Compressor Speed
Upper FAN
Lower FAN
Upper FAN
Lower FAN
L
Level 2
ow Noise Mode