EasyManuals Logo

Fujitsu UTP-VX90A User Manual

Fujitsu UTP-VX90A
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #158 background imageLoading...
Page #158 background image
Error Contents :
Main PCB Error
Symptom :
Error display [ C 1 ]
No operation.
Details :
Condition of occurrence : Communication error between CPU and Network Driver IC
Release condition : Communication is normal between CPU and Network Driver IC
Cause 1 : External noise
Upon pressing RESET button (SW7) or turning on power,
proceed as follows.
(1) If error did not appear, it is not a defect of PCB. Remove the
surrounding noise source.
(2) If error occurs again, check followings other than removing
surrounding noise source.
OK
Trouble shooting 80
Cause 2 : Signal Amplifier is defective.
Replace Signal Amplifier.
Signal Amplifier (UTY-VSGXZ1 )
04-88

Table of Contents

Other manuals for Fujitsu UTP-VX90A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTP-VX90A and is the answer not in the manual?

Fujitsu UTP-VX90A Specifications

General IconGeneral
BrandFujitsu
ModelUTP-VX90A
CategoryAir Conditioner
LanguageEnglish

Related product manuals