Error Contents :
Network communication Error
Symptom :
Error Code display [ 1 4 ]
OPERATION LED is flashing.
Details :
Condition of occurrence :
When the signal is cut off for more than 10 minutes from the registered Indoor unit (not including Slave unit).
Release condition : 1. The signal has been received from the Indoor units that was creating the error.
2. MPU has been booted up. (Release from the reset operation, the power failure stand-by operation.
Trouble shooting 94
Cause 1 : Connection failure
Check transmission cable
Check disconnected power line for Indoor unit.
Check if convertor power line is disconnected.
OK
OK
Cause 3 : Remote Controller is defective.
Replace Group Remote Controller.
Cause 2 : Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause
harmonic wave).
Group Remote Controller (UTY-CGGY / CGGG)
04-102

Table of Contents

Other manuals for Fujitsu UTP-VX90A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTP-VX90A and is the answer not in the manual?

Fujitsu UTP-VX90A Specifications

General IconGeneral
BrandFujitsu
ModelUTP-VX90A
CategoryAir Conditioner
LanguageEnglish

Related product manuals