EasyManua.ls Logo

Fujitsu UTP-VX90A - Page 91

Fujitsu UTP-VX90A
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trouble shooting 13 E31. 3
INDOOR UNIT Error Method:
Indoor unit Power Frequency
Abnormal
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 1 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
When 5 continuous failures occurred at Power frequency test.
Forecast of Cause :
1. Outside cause 2. Installation failure 3. Defective connection of electric components
4. Controller PCB defective
Check Point 2 : Check Installation condition
NO
Check Point 3 : Check connection of electric components
YES
Check Cable/Breaker
Check loose or removed connection
>> If Installation defect is found, correct it by referring
to Installation Manual.
OK
Check power supply voltage (AC198 - 264V between
Indoor unit terminal 1 and 2)
Check connection of Connector (any lose connector or
incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
Check Point 1-2 :
Check outside cause (Voltage drop or noise, etc.)
Instant drop ---- Check if there is a large load electric apparatus
in the same circuit.
Momentary power failure ----- Check if there is a defective
contact or leak current in the
power supply circuit.
Noise ----- Check if there is any equipment causing harmonic
wave near electric line (Neon bulb or electric
equipment that may cause harmonic wave).
Check the complete insulation of grounding.
Check Point 4 : Replace Controller PCB
Change Controller PCB and set up the original address.
AC
04-21

Table of Contents

Other manuals for Fujitsu UTP-VX90A

Related product manuals