Line Function
Setting range
or display
Setting
increment
Basic
setting
928 S Room in uence --, 1... 100 % 1 % 80 %
If the installation is tted with a room thermostat:
This function enables you to choose the ambient temperature's in uence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
932 S Room temp limitation --, 0.5... 4 °C 0.5 °C 0.5 °C
938 S Mixing valve decrease 0... 20 °C 1 °C 0 °C
941 S Actuator running time 30... 650 s 1 s 240 s
963 S With primary controller / system pump No, Yes No*
*Basic setting : 1 circuit = No ; 2 circuits = Yes.
Heating adjustment, Circuit 2
Only with the 2
nd
circuit kit option (If the installation consists of 2 heating circuits).
1010 U Comfort setpoint Reduced setpoint…
Comfort setpoint maximum
0.5 °C 20 °C
1012 U Reduced setpoint Frost protection setpoint…
Comfort setpoint
0.5 °C 19 °C
1014 U Frost protection setpoint 4 °C… Reduced setpoint 0.5 °C 8 °C
1016 S Comfort setpoint maximum Comfort temp... 35 °C 1 °C 28 °C
1020 I Heating curve slope
(see
g. 49, page 45)
0.1... 4 0.02 0.5
1021 I O -set of the heating curve
(
g. 50, page 45)
-4.5... 4.5 °C 0.5 °C 0 °C
1030 I Summer / Winter heating limits 8... 30 °C 0.5 °C 18 °C
When the average of the outdoor temperatures over the past 24 hours reaches 18°C, the regulator switches o the
heating (as an economy measure). During summer mode, the display shows "Eco". This function is only active in
automatic mode.
1040 I Flow temp setpoint min 8... Flow temp setpoint max 1 °C 17 °C
(with dynamic radiator, adjust from 30 to 35°C)
1041 I Flow temp setpoint max Flow temp setpoint min... 95 °C 1 °C 55 °C
Floor heating system = 50 °C / Radiators = 65 °C.
Important Note : Maximum temperature limitation is not a safety function as required by ground heating.
1050 S Room in uence 1 %... 100 % 1 % 50 %
If the installation is tted with a room thermostat:
This function enables you to choose the ambient temperature's in uence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1060 S Room temperature limitation 0.5... 4 °C 0.5 °C 0.5 °C
As soon as the room temperature = [Setpoint line 1010 (ex. 20°C) + Room temperature limitation setpoint line 1060
(ex. 0.5 °C)] > 20.5 °C => The heat pump is stopped.
It restarts when the room temperature falls below the setpoint (in the example, Room temperature < 20.0 °C).
1080 S Quick setback O , Down to reduced setpoint,
Down to frost prot setpoint
O
1090 S Optimum start control max 0... 360 min 10 min 180 min
1091 S Optimum stop control max 0... 360 min 10 min 30 min
1100 S Reduced setpoint increase start -30... 10 °C, -- 1 °C --
1101 S Reduced setpoint increase end -30... 10 °C, -- 1 °C -5 °C
1130 S Mixer valve increase 0... 50 °C 1 °C 0 °C
1134 S Actuator running time 30... 650 s 1 s 240 s
Waterstage Split Comfort DHW Serie / INSTALLATION / 2125 - EN