8. FIXATION PROCEDURE
a) Cut out the panel plate (Diagram 5 - item 15) where the controller is going to be installed, to a size where X =
71±0,5 mm and Y = 29±0,5 mm;
b) Remove the side clasps (Diagram 6 - item 15): to do this, press on the elliptical central part (with the Full
Gauge Controls) and slide the clasps back;
c) Pass the wires through the opening (Diagram 7 - item 15) and install the electrics as described in item 7;
d) Insert the controller into the opening made in the panel, from the outside;
e) Replace the clasps and move them until they are pressed against the panel, securing the controller to the
housing (see arrow in Diagram 6 - item 15);
f) Adjust the parameters as described in item 9.
WARNING: Where the installation needs to be sealed tight against liquids, the opening for the
controller must be more than 70.5x29mm. The side clasps must be secured in such a way as to create a
tight rubber seal that prevents any liquids entering the opening and the controller.
Protective Film - Diagram 9 (item 15)
This protects the controller when it is installed somewhere subject
IMPORTANT:Only apply it after you have finished making the electrical connections.
a) Pull the side clasps back (Diagram 6 - item 15);
b) Remove the protective film from the adhesive vinyl strip;
c) Apply the film to the entire upper part, folding the flaps, as indicated by the arrows - Diagram 9 (item 15);
d) Replace the clasps.
Note: The film is transparent, so that the electrical layout of the device can be seen.
9. OPERATIONS
9.1 Quick Access Menu Map
Press the ;key (short press) to navigate through the menu functions. Each press will display
the next function in the list. To confirm press the /(short press). The menu function map is
below:
FUNCTION SELECTION
;
FAST FREEZING (ON/OFF)
;
DEFROST (ON/OFF)
VIEW HOUR METER
;
;
;
ECONOMY SETPOINT (ON/OFF)
ADJUST DATE AND TIME
NORMAL SETPOINT
;
ECONOMY SETPOINT
;
EXIT FUNCTION
;
PROCESS VIEWER
VIEW VARIABLE
FAN VOLTAGE
VIEW HACCP ALARMS
;
;
;
;
DOOR OPENING
;
VIEW TEMPERATURE ON
SENSOR S2 (EVAPORATOR)
;
VIEW VOLTAGE
;
VIEW TEMPERATURE ON
SENSOR S3 (CONDENSER)
;
VIEW TEMPERATURE ON
SENSOR S4 (AUXILIARY)
BULB
;
ON / OFF DATALOGGER
(MANUAL MODE)
;
DISPLAYS VARIABLE
COMPRESSOR FREQ./ VOLTAGE
;
RESETTING HIGH AND LOW
PRESSURE ALARMS
;
SHUTDOWN OF CONTROL
FUNCTIONS
;
FUNCTION LOCK
;
;
7.1. Connecting the temperature sensors
- Connect sensor wires S1 to terminals "8 and 9", sensor wires S2 to terminals "10 and 11" and sensor
wires S3 to terminals ‘’12 and 13'’ and sensor wires S4 to terminals "14 and 7": polarity is indifferent.
- The length of the sensor cables can be increased by the user themselver by up to 200 meters, using a
2x24 AWG PP cable.
7.2. Recommendations from NBR5410 and IEC60364 standards
a) Install surge protectors to the controller’s power supply;
b) Install transient suppressors - supressor filter (type RC) - in the circuit to increase the working life of
the controller’s relay;
c) The sensor cables can be together, but not in the same conduit as the power supply for the controller
or the loads.
NEW CONNECTION SYSTEM (QUICK COUPLING):
PLUGABLE AND QUICK PUSH-IN
PUSH-IN CONNECTION:
- Hold the wire close to its end and insert it into the required opening
- If necessary, press the button to hel make the connection.
- Ferrule type terminals can be used. For the signal connections, the
ferrule must be at least 12mm. In power connectors the pin must be
at least 7mm.
PUSH-IN DISCONNECTION:
- To disconnect the wire, press the button
and remove it .
The wire must be stripped
5mm and tinned
Terminal Rocket Pin.
NOTE 1 - Signal Connectors:
-In connectors 1 to 14, the wire gauge must be between 0.2 and
1,5mm² (26 and 16AWG).
NOTE 2 - Power Connectors:
- In connectors 15 to 21, the wire gauge must be between 0.2 and
2.5mm² (26 and 12AWG).
9.2 List of Key Functions
The keys listed act as shortcuts for the following functions:
/
/
<
<
Short press: View date and time
Short press: Stop the audible alarm
Press for 2 seconds: Setpoint adjustment
Short press: Activate / Deactivate economy mode
Press for 4 seconds: Manual defrost
Press for 2 seconds: Enter the HACCP menu
Press for 2 seconds: Display of minimum and maximum temperatures
Short press: Turn on / off the lamp
;
;
;
Short press: enters the easy menu.
and
and
Press for 4 seconds: View process steps, temperature on sensors S2 / S3 /
S4 and current setpoint
/
/
<
<
Short press: Enter menu selection
<
<
<
<
Press for 2 seconds: When displaying temperature, compressor hour
meter or door opening number records, clears history
Press for 4 seconds: shutdown of control functions