INSTALLATION EDR-SOLA-IOM-2022-0216 SECTION 2
2-30
FIGURE 22  ROOF PENETRATION DETAILS
EN
EN
D
D
U
U
R
R
A
A
H
H
Y
Y
D
D
RONIC
RONIC
BOILER
BOILER
NOTES:
1) HORIZONTAL SECTIONS MUST ADHERE TO A MINIMUM
1/4 INCH PER FOOT (1 MM PER 48 MM) RISE TO RUN RATIO
2) MAINTAIN A MINIMUM 9 INCH (229 MM) AIR SPACE
CLEARANCE TO COMBUSTABLES, WIRE, AND INSULATION
3) INSTALL SUPPORT STRAPS AT 5 FT (152 CM) HORIZONTAL
INTERVALS AND AT ELBOWS
TYPICAL ROOF PENETRATIONS
COMBUSTION AIR FROM THE OUTDOORS
( SUGGESTED INSTALLATION CONFIGURATIONS )
MIN 4 FT
(122 CM)
ADJUSTABLE
FLASHING
METAL PLATE
FIRE STOP
ADJUSTABLE
FLASHING
ADHESIVE SEAL
STORM COLLAR
COMBUSTION
AIR INLET 90° ELBOW
1/2 INCH x 1/2 INCH
(13 MM x 13 MM)
MESH SCREEN
FLUE GAS EXHAUST TERMINATION
(RAIN CAP NOT REQUIRED)
IF SNOW ACCUMULATION
IS APPLICABLE, OPENING TO BE
MIN 1 FT (30 CM ) ABOVE
THIS NORMALLY EXPECTED LEVEL.
DO NOT PLACE INSULATION IN
REQUIRED AIR SPACE CLEARANCE
SCH40 PVC PIPE (TYPICAL)
REFERENCE TABLE 1 FOR
MIN CAI DIAMETER
STORM COLLAR
FLEXIBILE RUBBER
PIPE COUPLING
FLUE GAS EXHAUST
DIRECTION OF FLOW
COMBUSTION AIR INLET (CAI)
DIRECTION OF FLOW
STORM COLLAR
(FOR DOUBLE WALL)
MIN 4 FT (122 CM)
ABOVE AIR
INTAKE PIPING
UL-1738 APPROVED
EXHAUST VENT MATERIAL
LEVEL HOUSEKEEPING PAD
MIN 4 INCH (102 CM) HEIGHT
CONDENSATE TRAP
APPLIANCE ADAPTER
CONSULT FLUE MFG FOR SELECTION
REFERENCE TABLE 1 FOR FLUE GAS STACK DIAMETER
CAUTION:
SEPARATE AIR INTAKE AND EXHAUST TERMINATIONS AS FAR AS
POSSIBLE TO PREVENT FLUE GAS RECIRCULATION (FGR) DURING
DIFFERENT WIND CONDITIONS.
EXHAUST STACK IS DOWNWIND
OF AIR INTAKE OPENING