© Fulton Group N.A., Inc. 2022
3-8
OPERATION EDR-SOLA-IOM-2022-0216 SECTION 3
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document should substitute for full
review of documentation available
from the component manufacturer.
Endura boilers are factory test red
on natural gas. Propane operation
will require eld conversion to the
parameters in Table 10. Do not start
the boiler prior to fuel conversion or
damage may result.
Light O Low Fire High Fire
EDR-750
MBC1000 Supply Gas Press ("w.c.) - - 6.0 to 8.0
Enrichment Press. ("w.c.) 0.5 to 2.5 - -
Manifold Gas Press ("w.c.) - -0.2 to -0.4 -4.0 to -5.0
SOLA RPM 3000 to 3500 > 2000 < 8000
O % 2.0 to 3.5 6.0 to 7.5 5.0 to 6.0
Shutter Turns (# of Turns) - - 0.75 to 1.5
Oset Turns (# of Turns) - -2 to +2 -
Damper Position (deg) 20 to 30 - -
Light O Low Fire High Fire
EDR-1000
MBC1000 Supply Gas Press ("w.c.) - - 6.0 to 8.0
Enrichment Press. ("w.c.) 0.5 to 2.5 - -
Manifold Gas Press ("w.c.) - -0.2 to -0.4 -6.5 to -7.5
SOLA RPM 3000 to 3500 > 2000 < 10000
O % 2.0 to 4.5 6.0 to 7.5 5 to 6.0
Shutter Turns (# of Turns) - - 0.75 to 1.5
Oset Turns (# of Turns) - -2 to +2 -
Damper Position (deg) 20 to 30 - -
Light O Low Fire High Fire
EDR-1500
MBC2500 Supply Gas Press ("w.c.) - - 6.0 to 8.0
Enrichment Press. ("w.c.) 0.5 to 3.5 - -
Manifold Gas Press ("w.c.) - -0.2 to -0.4 -2.0 to -3.5
SOLA RPM 2600 to 3500 >2000 < 7500
O % 2.0 to 4.5 6.0 to 7.5 5.0 to 6.0
Shutter Turns (# of Turns) - - 1.5 to 3.0
Oset Turns (# of Turns) - -2 to +2 -
Damper Position (deg) 20 to 30 - -
Light O Low Fire High Fire
EDR-2000
MBC2500 Supply Gas Press ("w.c.) - - 6.0 to 8.0
Enrichment Press. ("w.c.) 0.5 to 3.5 - -
Manifold Gas Press ("w.c.) - -0.2 to -0.4 -4.5 to -5.2
SOLA RPM 2700 to 3500 > 2000 < 7500
O % 2.5 to 4.5 6.0 to 7.5 5.0 to 6.0
Shutter Turns (# of Turns) - - 2.5 to 4.0
Oset Turns (# of Turns) - -2 to +2 -
Damper Position (deg) 20 to 30 - -
TABLE 10 METAL WOVEN MESH BURNERS: VERIFICATION OF PROPANE COMBUSTION
16. Refer to Table 10 for parameters to commission the boiler for propane
operation. Burner turndown will be reduced when operating on propane.
Turndown
The burner is factory congured for up to 5:1 burner turndown. Wind eects
on combustion air supply and exhaust terminations, natural draft “stack eect”,
and gas delivery systems (among other site factors) will ultimately determine
what turndown settings are optimal for each application. Use a calibrated gas
ow meter (not supplied) to measure burner input rates. Consult your local
manufacturer’s representative or service organization with factory authorization
specic to the Endura product line for guidance.