3-32
OPERATION EDR-SOLA-IOM-2022-0216 SECTION 3
System Pump Enable/Disable Signal
The control may be congured to provide an enable/disable signal which can be
wired to a system pump control panel (not supplied). This will satisfy a sequence
to enable the system pumps when the boiler plant is not in the warm weather
shutdown or remote lead/lag disabled state.
Navigate to the master boiler Pump Conguration screen and select the pump
output contact where the eld wiring is terminated.
Tap the Advanced” button and check only the “Service active*” boxes
corresponding to Central Heat and Local Lead Lag. This ensures the contact will
remain active even when all boilers have satised the loop temperature and
burners are idle.
Opening the REMOTE LEAD/LAG ENABLE contacts at any time will disable the
boilers as well as the pump contact. If Warm Weather Shutdown is enabled, and
the outdoor air temperature reaches the shutdown Setpoint, the boilers and
pump contact will be disabled.
The REMOTE BOILER ENABLE contacts on the LCI circuit may be used to enable/
disable individual boilers and will not interfere with this contact.
FIGURE 74  SYSTEM PUMP CONTACT CONFIGURATION SCREEN
FIGURE 75  SYSTEM PUMP SERVICE ACTIVE CONFIGURATION SCREEN
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

Related product manuals