4-5
SECTION 4 EDR-SOLA-IOM-2022-0216 MAINTENANCE
Annual Maintenance Schedule
Annual maintenance must be performed prior to each heating season, and
includes but is not limited to the following tasks, which must be done by a
factory trained technician:
1. Inspect the fuel train, burner and control panel to be sure components are
free of debris and are properly attached to the boiler.
2. Replace the combustion air lter with a new lter of the same Fulton part
number (type, size and style).
3. Examine the venting system (air intake and exhaust piping).
Check all joints and pipe connections for tightness.
Check piping for corrosion or deterioration.
Check that the piping is clear of debris.
Check that the condensate drain system is functioning.
4. Inspect the hydronic heating system for other problems.
5. Leak test and inspect the lter of the gas valve. See Replacing Gas Valve
Internal Filter section of this manual.
6. Clean the low water cut-out probe on the water outlet pipe. This can be
accessed via the top removable panel.
7. Clean the venturi with a clean cloth to remove dust build up.
8. Remove and inspect burner. Clean as necessary. See Removing and
Cleaning Burner section of this manual.
9. Check the cabinet for leaks that would allow unltered combustion air to
enter the cabinet. Any leaks should be taped or caulked. Damaged gaskets
must be replaced.
10. Test relief valve per manufacturer instructions by lifting the lever for 5
seconds and allowing the valve to snap shut. Please see the manufacturer’s
recommendations on the relief valve tag.
11. Perform combustion analysis and adjust if necessary. A low O level can
indicate a need for burner service.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Never use open ame or other sources
of ignition to check for gas leaks.
Ensure boiler is o and cooled,
with proper lockout - tagout per
local codes prior to service and
maintenance.
4 CAUTION
Use caution when using any cleaning
solutions. Refer to local regulations for
proper cleaning solution disposal.
Do not allow dust or dirt to accumulate
around the boiler.