Questions? Please Contact Your Local Manufacturer’s Representative
4-7
SECTION 4 EDR-SOLA-IOM-2022-0216 MAINTENANCE
Removing and Cleaning Burner Assembly
Disassemble, inspect, and clean as follows:
1. Remove power and turn o gas supply. Allow the boiler to cool.
2. With the door open, place a ladder in front of the unit.
NOTE: The top of the electrical panel is not a step; it should not be used to support
a person’s weight.
3. Remove wires from ignition assembly.
4. Remove ignition assembly.
5. Remove UV Scanner.
6. Remove the (4) bolts between the fan transition and the premix elbow. Do
not removed the fan transition from the blower discharge.
7. Remove the (8) nuts and washers on burner ange.
NOTE: Due to unique hardware specications, alternate hardware must not be
substituted. If hardware is lost or damaged, contact your Fulton representative for
replacement.
8. Remove premix elbow.
9. Remove burner ange top gasket.
10. Remove burner by pulling up, making sure not to scrape the sides of the
burner. Place burner aside, ange side down.
NOTE: Do not use liquids or brushes when cleaning the burner.
11. Vacuum any visible debris inside the burner. Compressed air may also be
used, in moderation, to clean the pores of the woven material. Use the
following guidelines:
Dislodge any particulate matter from the burner surface matrix, keeping
the air nozzle about 2” from the burner’s surface and blowing straight
down the surface. Gently move the nozzle back and forth length-wise
above the surface. Avoid blowing air tangentially across the surface as this
may cause damage to burner surface. Allow particulate matter to fall from
the burner through the air/gas inlet. A vacuum may be used at the air/gas
inlet to assist in removing particulate matter.
12. If any burner damage is detected, contact your Fulton Representative.
Reassemble as follows:
1. Reassemble in reverse order.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Never use open ame or other sources
of ignition to check for gas leaks.
Ensure boiler is o and cooled,
with proper lockout - tagout per
local codes prior to service and
maintenance.
4 CAUTION
Use caution when using any cleaning
solutions. Refer to local regulations for
proper cleaning solution disposal.
Do not allow dust or dirt to accumulate
around the boiler.