EasyManua.ls Logo

FULTON VSRT Series - Technical Information: Recommended Water Conditions

FULTON VSRT Series
118 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDIX - A
Fulton Ltd
Capacities
(Applies to elevations up to
2,000 ft)
VSRT Model
VSRT-40
Rated Input at High Fire
kW
478
Minimum Input at Low Fire
kW
80
Rated Output
Boiler
HP
kg/hr
kW
40
626
392
Fuel
Requirements
(Pressure requirements at rated
input)
VSRT Model
VSRT-40
Fuel Usage at Rated Input
(Natural Gas)*
M
3
/hr
43
Fuel Usage at Rated Input
(Propane Gas)**
M
3
/hr
18.3
Min Gas Pressure (NG or
LPG)
mbar
19
Max Gas Pressure (NG or
LPG)
mbar
35
*m³/hr based on 40.1mJ/m³ Natural Gas (2016 Dukes Report)
**m³/hr based on 94mJ/m³ Propane
Electrical
Requirements
(Applies to <20ppm NO
x
standar
blower motor and control options
VSRT Model
VSRT-40
Electrical Supply*
volts
Ø
Hz
400
3
50
Control Voltage
Volts ac
110
IP Rating
54
Full Load Amps (FLA)
Amps
21.6
d
)
*Includes Burner fan motor, feedwater pump & standard control circuit.
Weights &
Water Volume
VSRT Model
VSRT-40
Dry Weight
kg
2,654
Operating Weight at
Normal Working Level
kg
3,959
Flooded Weight
kg
4,228
Water Volume at Normal
Working Level
Litres
1,306