APPENDIX - A
Fulton Ltd
Flue
Requirements
VSRT Model
VSRT-10
Open Flued (Type
B)
Minimum Allowable
Draft Pressure
Boiler Operating
in WC
kPa
-0.25
-0.062
Flue Gas Exhaust
Flow Rate at 125 psig
Standard CFM
Actual CFM
95
163
Emissions
Typical Natural Gas Operati
(Corrected to 3% O
2
, CO to
10ppm or less)
VSRT Model
VSRT-10
<20ppm NOx
condition
VSRT-10
15% excess
air
operation
NO
x
kg/hr
0.004
0.013
SOx
kg/hr
0.0001
0.0001
CO
kg/hr
0.0013
0.0013
on
be
Min
Clearances
(Local codes may
supersede Fulton
VSRT Model
VSRT-10
Side clearance from
Vessel PV
mm
609
Total Installed Height
Required for Burner
Removal
mm
250
No information provided in the document constitutes a guarantee, consult factor for any guarantees
VSRT Model
VSRT-10
Open Flued (Type
B)
Boiler Room Ventilation
for Combustion (free area)
Low Level Inlet
Cm
2
428
Boiler Room Ventilation
for Combustion (free area)
High Level Outlet
Cm
2
214
Typical Combustion
Air Intake Flow Rate
M3/hr
150
Air Intake and
Ventilation
Requirements
VSRT-IOMM-2019-1
Page 82