Set Par. 112 for the Number of Retries.
Default Value: 6 Range: 0 9 Increment: 1
After fault occurs, the AC drive can be reset/restarted automatically up to 10 times. Setting this
parameter to 0 will disable the reset/restart operation after any fault has occurred.
Set Par.113 for the Retry Waiting Time.
Default Value: 2.5 Range: 0 120.0 Sec. Increment: 0.1 Sec.
Sets the time
between restart attempts when Auto Rstrt Tries is set to a value other than zero.
Set Par. 114
for the Retry Selection.
Default Value: 1023 Range: 0 1023 Increment: 1
Settings 1: Ground Fault can be auto reset
2: Over Voltage can be auto reset
4: Over Current can be auto reset
8: Low Voltage can be auto reset
16: Motor Over Load can be auto reset
32: Drive Over Temperature can be auto reset
64: Drive Over Load can be auto reset
128: Current sensor Broken can be auto reset
256: EEPROM Broken can be auto reset
512: Software Over Voltage can be auto reset
Example:
If a “Ground Fault”, “Over Current” and “Drive Over Load” needs to be auto reset then Par 114
should be set to 69 (1+4+64). The default value is “1023” which means all faults can be auto reset.
Set Par. 115
for Reset Fault
Default Value: 0 Range: 0 2 Increment: 1
Settings 0: Idle State
1: Resets the active fault but does not clear any fault buffer
2: Resets the active fault and clears all fault buffers to “0”
Resets a fault and clears the fault buffer. Used primarily to clear a fault over network communications.