Pr.15 Heavy Final Speed Close (FSC)
Unit: 0.1 Hz
Default: 5.0 Hz
Range: 0 ~ 400.0 Hz
Pr.16 Heavy Door Nudging Speed
Unit: 0.1 Hz
Default: 9.0 Hz
Range: 0 ~ 400.0 Hz
Pr.17 Heavy Door Close Acceleration Time
Unit: 0.1 Sec
Default: 6.0
Range: 0 ~ 320.0 Sec
The Acceleration time is used to determine the time required for the AC drive to ramp from 0 Hz to
its reference frequency (Pr.50).
Pr.18 Heavy Door Close Deceleration Time
Unit: 0.1 Sec
Default: 10.0
Range: 0 ~ 320.0 Sec
The Deceleration time is used to determine the time required for the AC drive to decelerate from
the reference frequency (Pr.50) down to 0 Hz.
Pr.19 Heavy Door Stall Reverse Force (output current detection level)
Unit: (0.1 %)
Default: 1.2A
Range: 0 ~ 200.0 %rated
If the output current remains higher than this setting during AC drive operation, the output current
detection signal is on from the open collector output terminal of the AC drive.
Pr.31 Heavy Door Quick Stop on Reverse
Unit: 0.1 A
Default: 2.0A
Range: 0~180 %rated
This parameter determines the level of the DC braking current output to the motor during stopping.
Pr.32 Heavy Door Slow Start Open (SSO)
Unit: 0.1 Hz
Default: 5.0 Hz
Range: 0 ~ 400.0 Hz
Pr.33 Heavy Door High Speed Open (HSO)
Unit: 0.1 Hz
Default: 45.0 Hz
Range: 0 ~ 400.0 Hz
G.A.L. Manufacturing Corporation December, 2007