INSTALLATION OF STANDALONE TWIN
SW1 CC2
ON OFF
6
6 Datalink Endtermination ON, OFF
5
5 ON = Master Mode, OFF = Slave mode
4
4 Remote enable input function. ON (default) = Open circuit, OFF = Closed circuit
3
3
2
2 Fuse value in mains cabinet, see below table for settings
1
1
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
3
3 3 3 3 3 3
2 2 2 2 2 2 2
1 1 1 1 1 1 1
16 A 20 A 25 A 32 A 40 A 50 A 63 A
SW2 CC1, CC2
ON OFF
4
4 ON = Fixed cable, OFF = Outlet
3
3
2
2 MAX Ampere for outlet / cable, see below table for settings
1
1
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
3
3 3 3 3 3 3 3
2 2 2 2 2 2 2 2
1 1 1 1 1 1 1 1
6 A 10 A 13 A 16 A 20 A 25 A 29 A 32 A
Dip Switch Information
(figure 13)