Battery maintenance 
Batteries must be replaced periodically as recommended by the manufacturer. The 
useful life of the battery is approximately 4 years. Avoid the total discharge of the 
batteries. 
Battery test fail 
When the control panel indicates that the battery test has failed, check the following: 
•  That the battery leads are in good condition 
•  That the battery leads are connected securely and correctly at the battery and at 
the panel 
•  That the control panel event log does not indicate a mains failure in the last 
twenty-four hours 
If the leads are in good condition, all connections are correct, and the control panel 
continues to report that the test has failed twenty-four hours after the last mains 
failure, then the batteries should be replaced immediately. 
Replacing batteries 
To replace the batteries: 
1.  Disconnect and remove the existing batteries from the cabinet. 
2.  Install and connect the replacement batteries using the bridge provided. Observe 
correct polarity. 
Always use the recommended replacement batteries. Dispose of used batteries 
according the European regulations and/or instructions from local authorities.