Modifications reserved Page 58/99
OPM_SPE_XXX_10K_40K_8GB_V020.doc Operating Manual SitePro 10-15-20-30-40 kVA / S8
`Home\Setup\User
DISPLAY
UPS name : SitePro
Language : ENGLISH
V
LCD Display screen
UPS Name The user can choose the name of the UPS
model shown on the main page (max. 9
characters).
Language This parameter allows the choice of
language used to display the information.
Valid choices are: English, German, Italian,
Spanish, French, Finnish, Polish, Portuguese,
Czech, Slovakian, Chinese, Swedish, Russian
and Dutch.
`Home\Setup\User
SUPER ECO MODE
Enabled : N
DAY OF WEEK
d1 d2 d3 d4 d5 d6 d7
HOURS / DAY
24 24 12 12 12 12 12
SUPER ECO MODE screen
This screen is enabled only for a single UPS, not for an RPA
Parallel System.
Enabled
This parameter (values Y/N) enables or disables the
operation in SEM mode (Super Eco Mode).
If the value is Y and the current time is in the interval for the
current day, the SEM mode is active.
The activation / deactivation of SEM mode is indicated each time in the event list.
In order to check the inverter function, at least 1 minute of VFI mode must be programmed during the week (the
Y/N parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in VFI mode is not respected, the SEM mode will be disabled.
If the value is N, the UPS is normally operating in VFI / double conversion mode at all times.
DAY OF WEEK (d1 ÷ d7): Enabling time in function of weekdays
For the weekdays from d1 to d7 (Saturday to Friday) the edit mode (edit day) allows to define time intervals when
the UPS is operating in SEM mode.
The hour is given in 24-hour format.
These intervals are defined by:
SEM START: The hour of the day after which the SEM mode is enabled.
The SEM mode is enabled until the following SEM STOP time is reached (the SEM STOP time of
the same day if this is later than the SEM START time, the SEM STOP time of the following day
otherwise).
SEM STOP: The hour of the day before which the SEM mode is enabled.
The SEM mode is enabled starting from the preceding SEM START time (the SEM START time of the same day if this
is earlier than the SEM STOP time, the SEM START time of the previous day otherwise).
Identical times for SEM START and SEM STOP maintain the existing mode only in case the previous command was
SEM START and the following command will be SEM STOP.
HOURS / DAY:
The number of SEM mode hours per weekday (from d1 - Saturday to d7 - Friday) is displayed in the operation
mode parameter window (ceiling value).