64855 0x6116 Polarizing Mode 1 3 1 FC156 1 1
64856 0x6117 Polarizing Voltage 0 1 1 FC272 0 1
64857 0x6118 Pos-Seq Restraint 0 500 1 F3 63 1
64859 0x611A Forward ECA -90 90 1 ° F20 75 1
64860 0x611B Forward Limit Angle 40 90 1 ° F0 90 1
64861 0x611C Forward Pickup 50 30000 1 x CT F3 50 1
64862 0x611D Reverse Limit Angle 40 90 1 ° F0 90 1
64863 0x611E Reverse Pickup 50 30000 1 x CT F3 50 1
64864 0x611F Block 0 0xFFFFFFFF 1 FC142 0 1
64866 0x6121 Events 0 1 1 FC126 1 1
64867 0x6122 Targets 0 2 1 FC101 1 1
Ground TOC 1
64880 0x612F Name 0 65535 1 F60_26 GND TOC 1 26
64893 0x613C Function 0 4 1 FC100 0 1
64895 0x613E Input 0 1 1 FC256 0 1
64896 0x613F Pickup 50 30000 1 x CT F13 1000 1
64898 0x6141 Curve 0 21 1 FC161 2 1
64899 0x6142 TDM 5 60000 1 F2 100 1
64900 0x6143 Reset 0 1 1 FC265 0 1
64902 0x6145 Relays 0 0xFFFFFFFF 1 FC198 0 1
64904 0x6147 Block 0 0xFFFFFFFF 1 FC142 0 1
64906 0x6149 Events 0 1 1 FC126 1 1
64907 0x614A Targets 0 2 1 FC101 1 1
Ground IOC 1
65010 0x61B1 Name 0 65535 1 F60_26 GND IOC 1 26
65023 0x61BE Function 0 4 1 FC100 0 1
65026 0x61C1 Pickup 50 30000 1 x CT F13 1000 1
65029 0x61C4 Pickup Delay 0 6000000 1 s F13 0 1
65031 0x61C6 Dropout Delay 0 6000000 1 s F13 0 1
65033 0x61C8 Relays 0 0xFFFFFFFF 1 FC198 0 1
65035 0x61CA Block 0 0xFFFFFFFF 1 FC142 0 1
65037 0x61CC Events 0 1 1 FC126 1 1
65038 0x61CD Targets 0 2 1 FC101 1 1
Negative Sequence IOC 1
65770 0x64A9 Name 0 65535 1 F60_26 NegSeq IOC
1
26
65783 0x64B6 Function 0 4 1 FC100 0 1
65786 0x64B9 Pickup 50 30000 1 x CT F13 1000 1
65789 0x64BC Pickup Delay 0 6000000 1 s F13 0 1
65791 0x64BE Dropout Delay 0 6000000 1 s F13 0 1
65793 0x64C0 Relays 0 0xFFFFFFFF 1 FC198 0 1
65795 0x64C2 Block 0 0xFFFFFFFF 1 FC142 0 1
65797 0x64C4 Events 0 1 1 FC126 1 1
65798 0x64C5 Targets 0 2 1 FC101 1 1
Phase Reversal
66040 0x65B7 Name 0 65535 1 F60_26 Phase Rev 26