11-122 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP
66053 0x65C4 Function 0 4 1 FC100 0 1
66054 0x65C5 Pickup Delay 0 18000 1 s F2 100 1
66055 0x65C6 Dropout Delay 0 18000 1 s F2 100 1
66056 0x65C7 Block 0 0xFFFFFFFF 1 FC142 0 1
66058 0x65C9 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
66060 0x65CB Events 0 1 1 FC126 1 1
66061 0x65CC Targets 0 1 1 FC101 1 1
PUV 1
66080 0x65DF Name 0 65535 1 F60_26 Ph UV 1 26
66093 0x65EC Function 0 4 1 FC100 0 1
66096 0x65EF Mode 0 1 1 FC260 0 1
66097 0x65F0 Pickup 0 150 1 x VT F2 100 1
66098 0x65F1 Minimum Voltage 0 150 1 x VT F2 20 1
66099 0x65F2 Phases for Operation 0 2 1 FC261 0 1
66100 0x65F3 Undervoltage Curves 0 1 1 FC131 0 1
66101 0x65F4 Pickup Delay 0 6000000 1 s F13 1000 1
66103 0x65F6 Relays 0 0xFFFFFFFF 1 FC198 0 1
66105 0x65F8 Block 0 0xFFFFFFFF 1 FC142 0 1
66107 0x65FA Events 0 1 1 FC126 1 1
66108 0x65FB Targets 0 2 1 FC101 1 1
PUV 2
66119 0x6606 Name 0 65535 1 F60_26 Ph UV 2 26
66132 0x6613 Function 0 4 1 FC100 0 1
66135 0x6616 Mode 0 1 1 FC260 0 1
66136 0x6617 Pickup 0 150 1 x VT F2 100 1
66137 0x6618 Minimum Voltage 0 150 1 x VT F2 20 1
66138 0x6619 Phases for Operation 0 2 1 FC261 0 1
66139 0x661A Undervoltage Curves 0 1 1 FC131 0 1
66140 0x661B Pickup Delay 0 6000000 1 s F13 1000 1
66142 0x661D Relays 0 0xFFFFFFFF 1 FC198 0 1
66144 0x661F Block 0 0xFFFFFFFF 1 FC142 0 1
66146 0x6621 Events 0 1 1 FC126 1 1
66147 0x6622 Targets 0 2 1 FC101 1 1
POV 1
66260 0x6693 Name 0 65535 1 F60_26 Ph OV 1 26
66273 0x66A0 Function 0 4 1 FC100 0 1
66276 0x66A3 Mode 0 1 1 FC260 0 1
66277 0x66A4 Pickup 2 300 1 x VT F2 150 1
66278 0x66A5 Phases for Operation 0 2 1 FC261 0 1
66279 0x66A6 Pickup Delay 0 6000000 1 s F13 1000 1
66281 0x66A8 Dropout Delay 0 6000000 1 s F13 1000 1
66283 0x66AA Relays 0 0xFFFFFFFF 1 FC198 0 1
66285 0x66AC Block 0 0xFFFFFFFF 1 FC142 0 1
66287 0x66AE Events 0 1 1 FC126 1 1
66288 0x66AF Targets 0 2 1 FC101 1 1
POV 2
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in