11-132 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP
74719 0x879E Input 16 0 0xFFFFFFFF 1 FC142 0 1
74721 0x87A0 Latching 0 1 1 FC126 0 1
74722 0x87A1 Reset 0 0xFFFFFFFF 1 FC142 0 1
74724 0x87A3 Pickup Delay 0 6000000 1 s F13 0 1
74726 0x87A5 Dropout Delay 0 6000000 1 s F13 0 1
74728 0x87A7 Relays 0 0xFFFFFFFF 1 FC198 0 1
74730 0x87A9 Block 0 0xFFFFFFFF 1 FC142 0 1
74732 0x87AB Events 0 1 1 FC126 1 1
74733 0x87AC Targets 0 2 1 FC101 1 1
Breaker Failure 1 Setup
74750 0x87BD Function 0 4 1 FC262 0 1
74752 0x87BF PH Retrip Superv Pickup 50 30000 1 x CT F3 1000 1
74753 0x87C0 NTRL Retrip Superv
Pickup
50 30000 1 x CT F3 1000 1
74754 0x87C1 Supervision 0 2 1 FC263 0 1
74755 0x87C2 Breaker Closed 0 0xFFFFFFFF 1 FC142 0 1
74757 0x87C4 T1 Pickup Delay 0 6000000 1 s F13 120 1
74759 0x87C6 T2 Pickup Delay 0 6000000 1 s F13 120 1
74761 0x87C8 T3 Pickup Delay 0 6000000 1 s F13 120 1
74763 0x87CA Phase Highset Pickup 50 30000 1 x CT F3 1000 1
74764 0x87CB Neutral Highset Pickup 50 30000 1 x CT F3 1000 1
74765 0x87CC Lowset Delay 0 6000000 1 s F13 0 1
74767 0x87CE Phase Lowset Pickup 50 30000 1 x CT F3 1000 1
74768 0x87CF Neutral Lowset Pickup 50 30000 1 x CT F3 1000 1
74769 0x87D0 Dropout Delay 0 6000000 1 s F13 100 1
74771 0x87D2 Relays 0 0xFFFFFFFF 1 FC198 0 1
74773 0x87D4 Block 0 0xFFFFFFFF 1 FC142 0 1
74775 0x87D6 Events 0 1 1 FC126 1 1
74776 0x87D7 Targets 0 2 1 FC101 1 1
Breaker Failure 2 Setup
74790 0x87E5 Function 0 4 1 FC262 0 1
74792 0x87E7 PH Retrip Superv Pickup 50 30000 1 x CT F3 1000 1
74793 0x87E8 NTRL Retrip Superv
Pickup
50 30000 1 x CT F3 1000 1
74794 0x87E9 Supervision 0 2 1 FC263 0 1
74795 0x87EA Breaker Closed 0 0xFFFFFFFF 1 FC142 0 1
74797 0x87EC T1 Pickup Delay 0 6000000 1 s F13 120 1
74799 0x87EE T2 Pickup Delay 0 6000000 1 s F13 120 1
74801 0x87F0 T3 Pickup Delay 0 6000000 1 s F13 120 1
74803 0x87F2 Phase Highset Pickup 50 30000 1 x CT F3 1000 1
74804 0x87F3 Neutral Highset Pickup 50 30000 1 x CT F3 1000 1
74805 0x87F4 Lowset Delay 0 6000000 1 s F13 0 1
74807 0x87F6 Phase Lowset Pickup 50 30000 1 x CT F3 1000 1
74808 0x87F7 Neutral Lowset Pickup 50 30000 1 x CT F3 1000 1
74809 0x87F8 Dropout Delay 0 6000000 1 s F13 100 1
74811 0x87FA Relays 0 0xFFFFFFFF 1 FC198 0 1
74813 0x87FC Block 0 0xFFFFFFFF 1 FC142 0 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words

Other manuals for GE 869