CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 11-133
74815 0x87FE Events 0 1 1 FC126 1 1
74816 0x87FF Targets 0 2 1 FC101 1 1
Breaker Failure 3 Setup
74830 0x880D Function 0 4 1 FC262 0 1
74832 0x880F PH Retrip Superv Pickup 50 30000 1 x CT F3 1000 1
74833 0x8810 NTRL Retrip Superv
Pickup
50 30000 1 x CT F3 1000 1
74834 0x8811 Supervision 0 2 1 FC263 0 1
74835 0x8812 Breaker Closed 0 0xFFFFFFFF 1 FC142 0 1
74837 0x8814 T1 Pickup Delay 0 6000000 1 s F13 120 1
74839 0x8816 T2 Pickup Delay 0 6000000 1 s F13 120 1
74841 0x8818 T3 Pickup Delay 0 6000000 1 s F13 120 1
74843 0x881A Phase Highset Pickup 50 30000 1 x CT F3 1000 1
74844 0x881B Neutral Highset Pickup 50 30000 1 x CT F3 1000 1
74845 0x881C Lowset Delay 0 6000000 1 s F13 0 1
74847 0x881E Phase Lowset Pickup 50 30000 1 x CT F3 1000 1
74848 0x881F Neutral Lowset Pickup 50 30000 1 x CT F3 1000 1
74849 0x8820 Dropout Delay 0 6000000 1 s F13 100 1
74851 0x8822 Relays 0 0xFFFFFFFF 1 FC198 0 1
74853 0x8824 Block 0 0xFFFFFFFF 1 FC142 0 1
74855 0x8826 Events 0 1 1 FC126 1 1
74856 0x8827 Targets 0 2 1 FC101 1 1
Breaker Failure 1 Initiate
74880 0x883F External Initiate 0 0xFFFFFFFF 1 FC142 0 1
74882 0x8841 Initiate IN1 0 0xFFFFFFFF 1 FC142 0x80C002 1
74884 0x8843 Initiate IN2 0 0xFFFFFFFF 1 FC142 0 1
74886 0x8845 Initiate IN3 0 0xFFFFFFFF 1 FC142 0x80C602 1
74888 0x8847 Initiate IN4 0 0xFFFFFFFF 1 FC142 0x80C802 1
74890 0x8849 Initiate IN5 0 0xFFFFFFFF 1 FC142 0x80D802 1
74892 0x884B Initiate IN6 0 0xFFFFFFFF 1 FC142 0 1
74894 0x884D Initiate IN7 0 0xFFFFFFFF 1 FC142 0x80DE02 1
74896 0x884F Initiate IN8 0 0xFFFFFFFF 1 FC142 0x80E002 1
74898 0x8851 Initiate IN9 0 0xFFFFFFFF 1 FC142 0x80EC02 1
74900 0x8853 Initiate IN10 0 0xFFFFFFFF 1 FC142 0x80F202 1
74902 0x8855 Initiate IN11 0 0xFFFFFFFF 1 FC142 0 1
74904 0x8857 Initiate IN12 0 0xFFFFFFFF 1 FC142 0 1
74906 0x8859 Initiate IN13 0 0xFFFFFFFF 1 FC142 0 1
74908 0x885B Initiate IN14 0 0xFFFFFFFF 1 FC142 0 1
74910 0x885D Initiate IN15 0 0xFFFFFFFF 1 FC142 0 1
VT Fuse Fail 1
75990 0x8C95 Name 0 65535 1 F60_26 VT Fuse
Fail1
26
76003 0x8CA2 Function 0 4 1 FC100A 0 1
76005 0x8CA4 Relays 0 0xFFFFFFFF 1 FC198 0 1
76007 0x8CA6 Events 0 1 1 FC126 1 1
76008 0x8CA7 Targets 0 2 1 FC101 1 1
Trip Circuit 1 Monitoring
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default