CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 11-145
82080 0xA45F Phases for Operation 0 3 1 FC261A 0 1
82081 0xA460 Minimum Oper Current 3 100 1 x CT F2 10 1
82082 0xA461 Block 0 0xFFFFFFFF 1 FC142 0 1
82084 0xA463 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
82086 0xA465 Events 0 1 1 FC126 1 1
82087 0xA466 Targets 0 2 1 FC101 1 1
Harmonic Detection 3
82098 0xA471 Function 0 4 1 FC100A 0 1
82100 0xA473 Harmonic 0 4 1 FC374 0 1
82101 0xA474 Pickup 1 1000 1 % F1 200 1
82102 0xA475 Pickup Delay 0 60000000 1 s F13 0 1
82104 0xA477 Phases for Operation 0 3 1 FC261A 0 1
82105 0xA478 Minimum Oper Current 3 100 1 x CT F2 10 1
82106 0xA479 Block 0 0xFFFFFFFF 1 FC142 0 1
82108 0xA47B Output Relays 0 0xFFFFFFFF 1 FC198 0 1
82110 0xA47D Events 0 1 1 FC126 1 1
82111 0xA47E Targets 0 2 1 FC101 1 1
Harmonic Detection 4
82122 0xA489 Function 0 4 1 FC100A 0 1
82124 0xA48B Harmonic 0 4 1 FC374 0 1
82125 0xA48C Pickup 1 1000 1 % F1 200 1
82126 0xA48D Pickup Delay 0 60000000 1 s F13 0 1
82128 0xA48F Phases for Operation 0 3 1 FC261A 0 1
82129 0xA490 Minimum Oper Current 3 100 1 x CT F2 10 1
82130 0xA491 Block 0 0xFFFFFFFF 1 FC142 0 1
82132 0xA493 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
82134 0xA495 Events 0 1 1 FC126 1 1
82135 0xA496 Targets 0 2 1 FC101 1 1
Harmonic Detection 5
82146 0xA4A1 Function 0 4 1 FC100A 0 1
82148 0xA4A3 Harmonic 0 4 1 FC374 0 1
82149 0xA4A4 Pickup 1 1000 1 % F1 200 1
82150 0xA4A5 Pickup Delay 0 60000000 1 s F13 0 1
82152 0xA4A7 Phases for Operation 0 3 1 FC261A 0 1
82153 0xA4A8 Minimum Oper Current 3 100 1 x CT F2 10 1
82154 0xA4A9 Block 0 0xFFFFFFFF 1 FC142 0 1
82156 0xA4AB Output Relays 0 0xFFFFFFFF 1 FC198 0 1
82158 0xA4AD Events 0 1 1 FC126 1 1
82159 0xA4AE Targets 0 2 1 FC101 1 1
Harmonic Detection 6
82170 0xA4B9 Function 0 4 1 FC100A 0 1
82172 0xA4BB Harmonic 0 4 1 FC374 0 1
82173 0xA4BC Pickup 1 1000 1 % F1 200 1
82174 0xA4BD Pickup Delay 0 60000000 1 s F13 0 1
82176 0xA4BF Phases for Operation 0 3 1 FC261A 0 1
82177 0xA4C0 Minimum Oper Current 3 100 1 x CT F2 10 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words