11-144 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP
81965 0xA3EC Pre-set -2147483648 2147483647 1 F30 0 1
81967 0xA3EE Compare -2147483648 2147483647 1 F30 0 1
81969 0xA3F0 Up 0 0xFFFFFFFF 1 FC142 0 1
81971 0xA3F2 Down 0 0xFFFFFFFF 1 FC142 0 1
81973 0xA3F4 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
81975 0xA3F6 Reset 0 0xFFFFFFFF 1 FC142 0 1
81977 0xA3F8 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
81979 0xA3FA Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
81981 0xA3FC Block 0 0xFFFFFFFF 1 FC142 0 1
81983 0xA3FE HI 15 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
81985 0xA400 EQL 15 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
81987 0xA402 LO 15 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
81989 0xA404 Events 0 1 1 FC126 1 1
Digital Counter 16
81990 0xA405 Function 0 1 1 FC126 0 1
81991 0xA406 Name 0 65535 1 F60_26 Counter 16 26
82004 0xA413 Units 0 65535 1 F60_6 units 6
82007 0xA416 Pre-set -2147483648 2147483647 1 F30 0 1
82009 0xA418 Compare -2147483648 2147483647 1 F30 0 1
82011 0xA41A Up 0 0xFFFFFFFF 1 FC142 0 1
82013 0xA41C Down 0 0xFFFFFFFF 1 FC142 0 1
82015 0xA41E Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
82017 0xA420 Reset 0 0xFFFFFFFF 1 FC142 0 1
82019 0xA422 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
82021 0xA424 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
82023 0xA426 Block 0 0xFFFFFFFF 1 FC142 0 1
82025 0xA428 HI 16 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
82027 0xA42A EQL 16 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
82029 0xA42C LO 16 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
82031 0xA42E Events 0 1 1 FC126 1 1
Harmonic Detection 1
82050 0xA441 Function 0 4 1 FC100A 0 1
82052 0xA443 Harmonic 0 4 1 FC374 0 1
82053 0xA444 Pickup 1 1000 1 % F1 200 1
82054 0xA445 Pickup Delay 0 60000000 1 s F13 0 1
82056 0xA447 Phases for Operation 0 3 1 FC261A 0 1
82057 0xA448 Minimum Oper Current 3 100 1 x CT F2 10 1
82058 0xA449 Block 0 0xFFFFFFFF 1 FC142 0 1
82060 0xA44B Output Relays 0 0xFFFFFFFF 1 FC198 0 1
82062 0xA44D Events 0 1 1 FC126 1 1
82063 0xA44E Targets 0 2 1 FC101 1 1
Harmonic Detection 2
82074 0xA459 Function 0 4 1 FC100A 0 1
82076 0xA45B Harmonic 0 4 1 FC374 0 1
82077 0xA45C Pickup 1 1000 1 % F1 200 1
82078 0xA45D Pickup Delay 0 60000000 1 s F13 0 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words