Low-Voltage Power Circuit Breakers
Type WavePro
TM
with
Enhanced MicroVersaTrip Plus
TM
,
MicroVersaTrip PM
TM
(Series RMS-9D),
or Power+
TM
Digital RMS Trip Units
Long-Time Delay, Short-Time Delay,
and Instantaneous Time-Current Curves
Curves apply at 50 to 60 Hertz and
from -20°C to 55°C Breaker ambient.
-20°C to 70°C trip unit ambient.
Settings Glossary
S or CT = Current Sensor Rating in amps
C or LT = Current Setting in amps
X or I
n
= Rating Plug Rating in amps
MicroVersaTrip Plus & PM Adjustments
Long-Time Function:
• Current settings (C): 0.5 to 1.1 in 0.05 increments
and are multiples of the rating plug amps (X).
Delay bands: 1, 2, 3, and 4
Short-Time Function
• Pickup settings: 1.5 to 9.0 in 0.5 increments
and are multiples of the current setting (C).
Delay bands (I
2
t In & Out): 1 = Min, 2 = Int, 3 = Max
Instantaneous Function:
• See table and curve above.
Power+ Adjustments
Long-Time Function:
• Current settings (C): 0.5, .6, .7, .8, .9, .95, 1, 1.1
and are multiples of the rating plug amps (X).
Delay bands: 1, 2, 3, and 4
Short-Time Function
• Pickup setting: 1.5, 2, 2.5, 3, 4, 5, 7, 9 and are
multiples of the current setting (C).
Delay bands (I
2
t In & Out): 1 = Min, 2 = Int, 3 = Max
Instantaneous Function:
• See table and curve above.
GE Consumer & Industrial -
Electrical Distribution
DES-001B
DES-001B
DES-001B
Available Ratings (Amperes)
Breaker Current
Sensor
Type Model Frame (S) = CT Rating Plug (X) = I
n
150 60*, 80, 100, 125, 150
WP08 800 400 150*, 200, 225, 250, 300, 400
800 300*, 400, 450*, 500, 600, 700, 800
800 300*, 400, 450*, 500, 600, 700, 800
LVPCB
WP16 1600
1600 600*, 800, 1000, 1100*, 1200, 1600
WP20 2000 2000 750*, 800*, 1000, 1200, 1500*, 1600, 2000
WP32 3200 3200 1200, 1600, 2400, 3200
WP40 4000 4000 1600, 2000, 2500, 3000, 3600*, 4000
WP50* 5000 5000 3200, 4000, 5000
* Not available for Power+™
Voltage Rating: 600 Vac, nominal
4 4
8.0
3.5
4.5
5.5
7.5
6.5
8.5
Max (3)
M
in (1)
Int (2)
1.5
Application
D
etermines
End of Curve
.5 .6 .7 .8 .9 2 3 4 5 6 7 81
9
10 20 30 40 50 60 70 80 90
100
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
1
.9
.8
.7
.
6
.5
.4
.
3
.2
.1
.09
.08
.07
.
06
.
05
.
04
.
03
.02
.01
.5 .6 .7 .8 .9 2 3 4 5 6 7 81
9
10 20 30 40 50 60 70 80 90
100
MULTIPLES OF CURRENT SETTING (C)
MULTIPLES OF CURRENT SETTING (C)
TIME IN SECONDS
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
1
.
9
.8
.7
.6
.5
.
4
.
3
.
2
.
1
.
09
.
08
.07
.
06
.
05
.
04
.03
.
02
.01
TIME IN SECONDS
3
2
1
.9
.8
.7
.6
.
5
.4
.
3
.
2
.
1
.09
.
08
.
07
.06
.
05
.04
.03
.02
.01
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8
9
10 20 30
3
2
1
.9
.8
.7
.6
.
5
.4
.
3
.
2
.
1
.09
.
08
.
07
.06
.
05
.04
.03
.02
.01
TIME IN SECONDS
MULTIPLES OF INSTANTANEOUS PICKUP SETTING
I
2
t Out
Application
Determines
End of Curve
Power+ Instantaneous Pickup Settings in Multiples of Rating Plug Amps (X)
Pickup Settings on Power+ Trip Units without Short-Time Function
For (S) = 800 to 3200 A: 1.5, 2, 3, 5, 7, 9, 10
For (S) = 4000 A: 1.5, 2, 3, 5, 7, 9
Pickup Settings on Power+ Trip Units with Short-Time Function
For (S) = 800 to 2000 A: 1.5, 2, 3, 5, 7, 9, 10, 13, 15
For (S) = 3200 A: 1.5, 2, 3, 5, 7, 9, 10, 13
For (S) = 4000 A: 1.5, 2, 3, 5, 7, 9
Minimum Total
Clearing Time
Maximum Total
Clearing Time
Short
Time
2.0
3.0
4
5.0
6.0
7.0
2.5
9.0
MVT Instantaneous Pickup Settings in Multiples of Rating Plug Amps (X)
Pickup Settings on MVT Trip Units without Short-Time Function:
For (S) = 150 to 3200 A: 1.5 to 10 in increments of 0.5
For (S) = 4000 A: 1.5 to 9 in increments of 0.5
For (S) = 5000 A: 1.5 to 7 in increments of 0.5
Pickup Settings on MVT Trip Units with Short-Time Function:
For (S) = 150 to 2000 A: 1.5 to 15 in increments of 0.5
F
or (S) = 3200 A: 1.5 to 13 in increments of 0.5
For (S) = 4000 A: 1.5 to 9 in increments of 0.5
For (S) = 5000 A: 1.5 to 7 in increments of 0.5
Long-Time
Delay Bands
I
2
t
In
4
1
2
3