40
35"
3200A
800-
1600A
CABLE CONNECTED
TIE
38" 38"
BUS CONNECTED
TIE
MT30-20
BUS CONNECTED
TIE
30"
TIE
7"
3200A
35"
CABLE CONNECTED
5000A MAIN OR TIE
800-
1600A
21"
21"
800-
1600A
MT38-6
MT30-21
30"
7"
3200-
4000A
TIE
35"
MT30-22
30"
TIE
CABLE CONNECTED
5000A MAIN OR TIE
42"
MT38-7
8
1" MINIMUM DEPTH WITH 5000A
B
REAKERS AND CABLE CONNECTIONS
MAIN
TIE
21"
3
5"
5000A
28"
8
1" MINIMUM DEPTH WITH 5000A
B
REAKERS AND CABLE CONNECTIONS
MAIN
TIE
21"
3
5"
5000A
28"
9
2"
MT30-23
BUS CONNECTED
TIE
30"
7"
TIE
21"
800-
1600A
35"
3200A
21"
21"
800-
1600A
****
** **
21"
7"
92"
BUS
LOWER
M
ID
BUS
*
UPPER
BUS
CABLE CONNECTION (OTHER THAN FEEDER BREAKER)
INCOMING
OUTGOING
MID BUS LEVEL IS NOT AVAILABLE AT 5000A
(USE ONLY UPPER OR LOWER BUS LEVELS)
LEGEND & NOTES
*
FEEDER CABLE CONNECTION
BUSWAY CONNECTION
B/W
FEEDER CUBICLES ARE NOT AVAILABLE WHEN
3200A AND 4000A BREAKERS HAVE 100KA
SHORT CIRCUIT RATING
**
30/38” Main/tie sections