5-46 B30 Bus Differential System GE Multilin
5.2 PRODUCT SETUP 5 SETTINGS
5
The B30 Bus Differential System is provided with optional Ethernet Global Data (EGD) communications
capability. This feature is specified as a software option at the time of ordering. See the Ordering section
of chapter 2 for additional details.
The relay supports one fast Ethernet Global Data (EGD) exchange and two slow EGD exchanges. There are 20 data items
in the fast-produced EGD exchange and 50 data items in each slow-produced exchange.
Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes.
The relay can be configured to ‘produce’ EGD data exchanges, and other devices can be configured to ‘consume’ EGD
data exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the
exchange production rate can be configured.
EGD cannot be used to transfer data between UR-series relays. The relay supports EGD production only. An EGD
exchange will not be transmitted unless the destination address is non-zero, and at least the first data item address is set to
a valid Modbus register address. Note that the default setting value of “0” is considered invalid.
The settings menu for the fast EGD exchange is shown below:
PATH: SETTINGS PRODUCT SETUP  COMMUNICATIONS  EGD PROTOCOL FAST PROD EXCH 1 CONFIGURATION
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The B30 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).
FAST PROD EXCH 1
CONFIGURATION
EXCH 1 FUNCTION:
Disable
Range: Disable, Enable
MESSAGE
EXCH 1 DESTINATION:
0.0.0.0
Range: standard IP address
MESSAGE
EXCH 1 DATA RATE:
1000 ms
Range: 50 to 1000 ms in steps of 1
MESSAGE
EXCH 1 DATA ITEM 1:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range)
MESSAGE
EXCH 1 DATA ITEM 2:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range)
MESSAGE
EXCH 1 DATA ITEM 3:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range)
MESSAGE
EXCH 1 DATA ITEM 20:
0
Range: 0 to 65535 in steps of 1
(Modbus register address range)