7-2 B30 Bus Differential System GE Multilin
7.1 COMMANDS 7 COMMANDS AND TARGETS
7
7.1.3 CLEAR RECORDS
PATH: COMMANDS  CLEAR RECORDS
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.
7.1.4 SET DATE AND TIME
PATH: COMMANDS  SET DATE AND TIME
The date and time can be entered here via the faceplate keypad, but if the relay is synchronizing to an external time source
such as PTP, IRIGB or SNTP, the manually entered time will be quickly over-written. The time setting is based on the 24-
hour  clock. The complete date, as a minimum, must be entered to allow execution of this command. The new time (if
entered) and date will take effect at the moment the ENTER key is clicked.
The timescale of the entered time should be local time, including daylight time where and when applicable.
7.1.5 RELAY MAINTENANCE
PATH: COMMANDS  RELAY MAINTENANCE
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated
by changing a command setting to “Yes” and pressing the ENTER key. The command setting will then automatically revert
to “No”. The service command is activated by entering a numerical code and pressing the ENTER key.
 COMMANDS
 CLEAR RECORDS
CLEAR USER FAULT
REPORTS? No
Range: No, Yes
CLEAR EVENT RECORDS?
No
Range: No, Yes
CLEAR OSCILLOGRAPHY?
No
Range: No, Yes
CLEAR UNAUTHORIZED
ACCESS? No
Range: No, Yes
CLEAR DIRECT I/O
COUNTERS? No
Range: No, Yes. Valid only for units with Direct Input/
Output module.
CLEAR TELEPROTECT
COUNTERS? No
Range: No, Yes
CLEAR ALL RELAY
RECORDS? No
Range: No, Yes
 COMMANDS
 SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03
(YYYY/MM/DD HH:MM:SS)
 COMMANDS
 RELAY MAINTENANCE
PERFORM LAMPTEST?
No
Range: No, Yes
UPDATE ORDER CODE?
No
Range: No, Yes
REBOOT RELAY?
No
Range: No, Yes
SERVICE COMMAND:
    0
Range: 0, 101
SAVE VOLATILE DATA?
No
Range: No, Yes