GE Multilin B30 Bus Differential System 9-11
9 THEORY OF OPERATION 9.6 OUTPUT LOGIC AND EXAMPLES
9
Figure 9–10: EXTERNAL FAULT EXAMPLE
836735A1.CDR
The bus differential
protection element
picks up due to heavy
CT saturation
The CT saturation flag
is set safely before the
pickup flag
The element
does not
maloperate
The
directional flag
is not set
0.06 0.07 0.08 0.09 0.1 0.11 0.12
-200
-150
-100
-50
0
50
100
150
200
~1 ms
Despite heavy CT
saturation the
external fault current
is seen in the
opposite direction