B-12 B30 Bus Differential System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
Platform Direct Input/Output States (Read Only)
15C0 Direct Input States (6 items) 0 to 65535 --- 1 F500 0
15C8 Direct Outputs Average Message Return Time 1 0 to 65535 ms 1 F001 0
15C9 Direct Outputs Average Message Return Time 2 0 to 65535 ms 1 F001 0
15CA Direct Inputs/Outputs Unreturned Message Count -
Ch. 1
0 to 65535 --- 1 F001 0
15CB Direct Inputs/Outputs Unreturned Message Count -
Ch. 2
0 to 65535 --- 1 F001 0
15D0 Direct Device States 0 to 65535 --- 1 F500 0
15D1 Reserved 0 to 65535 --- 1 F001 0
15D2 Direct Inputs/Outputs CRC Fail Count 1 0 to 65535 --- 1 F001 0
15D3 Direct Inputs/Outputs CRC Fail Count 2 0 to 65535 --- 1 F001 0
Field Unit Input/Output States (Read Only)
15E0 Field Unit Contact Input States (3 items) 0 to 65535 --- 1 F500 0
15E3 Field Unit Contact Input Output Operand States (8
items)
0 to 65535 --- 1 F500 0
15EB Field Contact Output Physical States (8 items) 0 to 65535 --- 1 F500 0
15F3 Field Contact Output Current States (8 items) 0 to 65535 --- 1 F500 0
15FB Field Contact Output Physical States (8 items) 0 to 65535 --- 1 F500 0
1603 Field Shared Input States 0 to 65535 --- 1 F500 0
1604 Field Shared Input Channel States 0 to 65535 --- 1 F500 0
1605 Field Shared Input Test States 0 to 65535 --- 1 F500 0
1606 Field Shared Output Operand States 0 to 65535 --- 1 F500 0
1607 Field Latching Output Open Operand States 0 to 65535 --- 1 F500 0
1608 Field Latching Output Close Operand States 0 to 65535 --- 1 F500 0
1609 Field Latching Output Open Driver States 0 to 65535 --- 1 F500 0
160A Field Latching Output Close Driver States 0 to 65535 --- 1 F500 0
160B Field Latching Output Physical States 0 to 65535 --- 1 F500 0
160C Field Unit Online/Offline States 0 to 65535 --- 1 F500 0
160D Field RTD Input Trouble States 0 to 65535 --- 1 F500 0
160E Field Transducer Input Trouble States 0 to 65535 --- 1 F500 0
Ethernet Fibre Channel Status (Read Only)
1610 Ethernet Primary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
1611 Ethernet Secondary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
1612 Ethernet Tertiary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
Field Unit RTD Actuals (Read Only) (8 modules)
16C0 Field RTD x Value -32768 to 32767 °C 1 F002 0
16C1 ...Repeated for module number 2
16C2 ...Repeated for module number 3
16C3 ...Repeated for module number 4
16C4 ...Repeated for module number 5
16C5 ...Repeated for module number 6
16C6 ...Repeated for module number 7
16C7 ...Repeated for module number 8
Field Unit Transducer Actuals (Read Only) (8 modules)
16C8 Field Transducer 1 Value -32.768 to 32.767 --- 0.001 F004 0
16CA ...Repeated for Field Transducer 2
16CC ...Repeated for Field Transducer 3
16CE ...Repeated for Field Transducer 4
16D0 ...Repeated for Field Transducer 5
Table B–10: MODBUS MEMORY MAP (Sheet 4 of 60)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT