B-14 B30 Bus Differential System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
1A1A Source 1 Phase BC or BA Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A1B Source 1 Phase CA or CB Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A1D Source 1 Phase CA or CB Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A1E Source 1 Auxiliary Voltage RMS 0 to 999999.999 V 0.001 F060 0
1A20 Source 1 Auxiliary Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A22 Source 1 Auxiliary Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A23 Source 1 Zero Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A25 Source 1 Zero Sequence Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A26 Source 1 Positive Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A28 Source 1 Positive Sequence Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A29 Source 1 Negative Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A2B Source 1 Negative Sequence Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A2C Reserved (20 items) --- --- --- F001 0
1A40 ...Repeated for Source 2
1A80 ...Repeated for Source 3
1AC0 ...Repeated for Source 4
1B00 ...Repeated for Source 5
1B40 ...Repeated for Source 6
Source Frequency (Read Only) (6 modules)
1D80 Frequency for Source 1 2 to 90 Hz 0.001 F003 0
1D82 Frequency for Source 2 2 to 90 Hz 0.001 F003 0
1D84 Frequency for Source 3 2 to 90 Hz 0.001 F003 0
1D86 Frequency for Source 4 2 to 90 Hz 0.001 F003 0
1D88 Frequency for Source 5 2 to 90 Hz 0.001 F003 0
1D8A Frequency for Source 6 2 to 90 Hz 0.001 F003 0
Breaker Flashover (Read/Write Setting) (2 modules)
2196 Breaker Flashover 1 Function 0 to 1 --- 1 F102 0 (Disabled)
2197 Breaker Flashover 1 Side 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
2198 Breaker Flashover 1 Side 2 Source 0 to 6 --- 1 F211 0 (None)
2199 Breaker Flashover 1 Status Closed A 0 to 4294967295 --- 1 F300 0
219B Breaker Flashover 1 Status Closed B 0 to 4294967295 --- 1 F300 0
219D Breaker Flashover 1 Status Closed C 0 to 4294967295 --- 1 F300 0
219F Breaker Flashover 1 Voltage Pickup Level 0 to 1.5 pu 0.001 F001 850
21A0 Breaker Flashover 1 Voltage Difference Pickup
Level
0 to 100000 V 1 F060 1000
21A2 Breaker Flashover 1 Current Pickup Level 0 to 1.5 pu 0.001 F001 600
21A3 Breaker Flashover 1 Pickup Delay 0 to 65.535 s 0.001 F001 100
21A4 Breaker Flashover 1 Supervision Phase A 0 to 4294967295 --- 1 F300 0
21A6 Breaker Flashover 1 Supervision Phase B 0 to 4294967295 --- 1 F300 0
21A8 Breaker Flashover 1 Supervision Phase C 0 to 4294967295 --- 1 F300 0
21AA Breaker Flashover 1 Block 0 to 4294967295 --- 1 F300 0
21AC Breaker Flashover 1 Events 0 to 1 --- 1 F102 0 (Disabled)
21AD Breaker Flashover 1 Target 0 to 2 --- 1 F109 0 (Self-Reset)
21AE Reserved (4 items) --- --- --- F001 0
21B2 ...Repeated for Breaker Flashover 2
Passwords Unauthorized Access (Read/Write Command)
2230 Reset Unauthorized Access 0 to 1 --- 1 F126 0 (No)
Field Unit Raw Data Settings (Read/Write Setting)
2460 Field Raw Data Port 0 to 7 --- 1 F244 6 (H1a)
2461 Field Raw Data Freeze 0 to 1 --- 1 F102 0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 6 of 60)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT