B-26 B30 Bus Differential System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
40AB DNP Unsolicited Responses Maximum Retries 1 to 255 --- 1 F001 10
40AC DNP Unsolicited Responses Destination Address 0 to 65519 --- 1 F001 1
40AD Ethernet Operation Mode 0 to 1 --- 1 F192 1 (Full-
Duplex)
40AE DNP Current Scale Factor 0 to 8 --- 1 F194 2 (1)
40AF DNP Voltage Scale Factor 0 to 8 --- 1 F194 2 (1)
40B0 DNP Power Scale Factor 0 to 8 --- 1 F194 2 (1)
40B1 DNP Energy Scale Factor 0 to 8 --- 1 F194 2 (1)
40B2 DNP Power Scale Factor 0 to 8 --- 1 F194 2 (1)
40B3 DNP Other Scale Factor 0 to 8 --- 1 F194 2 (1)
40B4 DNP Current Default Deadband 0 to 100000000 --- 1 F003 30000
40B6 DNP Voltage Default Deadband 0 to 100000000 --- 1 F003 30000
40B8 DNP Power Default Deadband 0 to 100000000 --- 1 F003 30000
40BA DNP Energy Default Deadband 0 to 100000000 --- 1 F003 30000
40BC DNP Power Factor Default Deadband 0 to 100000000 -- 1 F003 30000
40BE DNP Other Default Deadband 0 to 100000000 --- 1 F003 30000
40C0 DNP IIN Time Synchronization Bit Period 1 to 10080 min 1 F001 1440
40C1 DNP Message Fragment Size 30 to 2048 --- 1 F001 240
40C2 DNP Client Address 3 0 to 4294967295 --- 1 F003 0
40C4 DNP Client Address 4 0 to 4294967295 --- 1 F003 0
40C6 DNP Client Address 5 0 to 4294967295 --- 1 F003 0
40C8 DNP Number of Paired Binary Output Control
Points
0 to 32 --- 1 F001 0
40C9 DNP TCP Connection Timeout 10 to 7200 s 1 F001 120
40CA DNP Communications Reserved (22 items) 0 to 1 --- 1 F001 0
40E0 TCP Port Number for the IEC 60870-5-104
Protocol
0 to 65535 --- 1 F001 2404
40E1 IEC 60870-5-104 Protocol Function 0 to 1 --- 1 F102 0 (Disabled)
40E2 IEC 60870-5-104 Protocol Common Address of
ASDU
0 to 65535 --- 1 F001 0
40E3 IEC 60870-5-104 Protocol Cyclic Data
Transmission Period
1 to 65535 s 1 F001 60
40E4 IEC 60870-5-104 Current Default Threshold 0 to 100000000 --- 1 F003 30000
40E6 IEC 60870-5-104 Voltage Default Threshold 0 to 100000000 --- 1 F003 30000
40E8 IEC 60870-5-104 Power Default Threshold 0 to 100000000 --- 1 F003 30000
40EA IEC 60870-5-104 Energy Default Threshold 0 to 100000000 --- 1 F003 30000
40EC IEC 60870-5-104 Power Factor Default Threshold 0 to1 --- 0.01 F001 100
40EE IEC 60870-5-104 Other Default Threshold 0 to 100000000 --- 1 F003 30000
40F0 IEC 60870-5-104 Client Address (5 items) 0 to 4294967295 --- 1 F003 0
4104 IEC 60870-5-104 Redundancy Port Enabled/
Disabled
0 to 1 --- 1 F126 0 (No)
4105 Port 2 IP Address 0 to 4294967295 --- 1 F003 56554706
4107 Port 2 IP Subnet Mask 0 to 4294967295 --- 1 F003 4294966272
4109 Port 2 Gateway IP Address 0 to 4294967295 --- 1 F003 56554497
410B PRT2 Ethernet Operation Mode 0 to 1 --- 1 F192 1 (Full-
Duplex)
410C PRT2 Redundancy Enabled 0 to 1 --- 1 F126 0 (No)
410D Port 3 IP Address 0 to 4294967295 --- 1 F003 56554706
410F Port 3 IP Subnet Mask 0 to 4294967295 --- 1 F003 4294966272
4111 Port 3 Gateway IP Address 0 to 4294967295 --- 1 F003 56554497
4113 Port 3 Ethernet Operation Mode 0 to 1 --- 1 F192 1 (Full-
Duplex)
Table B–10: MODBUS MEMORY MAP (Sheet 18 of 60)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents