B-38 B30 Bus Differential System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
74A4 Disconnect Switch 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)
74A5 Disconnect Switch 1 Open 0 to 4294967295 --- 1 F300 0
74A7 Disconnect Switch 1 Block Open 0 to 4294967295 --- 1 F300 0
74A9 Disconnect Switch 1 Close 0 to 4294967295 --- 1 F300 0
74AB Disconnect Switch 1 Block Close 0 to 4294967295 --- 1 F300 0
74AD Disconnect Switch 1 Phase A / Three-pole Closed 0 to 4294967295 --- 1 F300 0
74AF Disconnect Switch 1 Phase A / Three-pole Opened 0 to 4294967295 --- 1 F300 0
74B1 Disconnect Switch 1 Phase B Closed 0 to 4294967295 --- 1 F300 0
74B3 Disconnect Switch 1 Phase B Opened 0 to 4294967295 --- 1 F300 0
74B5 Disconnect Switch 1 Phase C Closed 0 to 4294967295 --- 1 F300 0
74B7 Disconnect Switch 1 Phase C Opened 0 to 4294967295 --- 1 F300 0
74B9 Disconnect Switch 1 Operate Time 0 to 65.535 s 0.001 F001 70
74BA Disconnect Switch 1 Alarm Delay 0 to 65.535 s 0.001 F003 0
74BC Disconnect Switch 1 Events 0 to 1 --- 1 F102 0 (Disabled)
74BD Reserved (2 items) --- --- --- F001 0
74BF ...Repeated for Disconnect Switch 2
74DE ...Repeated for Disconnect Switch 3
74FD ...Repeated for Disconnect Switch 4
751C ...Repeated for Disconnect Switch 5
753B ...Repeated for Disconnect Switch 6
755A ...Repeated for Disconnect Switch 7
7579 ...Repeated for Disconnect Switch 8
7598 ...Repeated for Disconnect Switch 9
75B7 ...Repeated for Disconnect Switch 10
75D6 ...Repeated for Disconnect Switch 11
75F5 ...Repeated for Disconnect Switch 12
7614 ...Repeated for Disconnect Switch 13
7633 ...Repeated for Disconnect Switch 14
7652 ...Repeated for Disconnect Switch 15
7671 ...Repeated for Disconnect Switch 16
7690 ...Repeated for Disconnect Switch 17
76AF ...Repeated for Disconnect Switch 18
76CE ...Repeated for Disconnect Switch 19
76ED ...Repeated for Disconnect Switch 20
770C ...Repeated for Disconnect Switch 21
772B ...Repeated for Disconnect Switch 22
774A ...Repeated for Disconnect Switch 23
7769 ...Repeated for Disconnect Switch 24
Thermal Overload Protection (Read/Write Settings) (2 modules)
7788 Thermal Protection 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7789 Thermal Protection 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
778A Thermal Protection 1 Base Current 0.2 to 3 pu 0.01 F001 80
778B Thermal Protection 1 K Factor 1 to 1.2 --- 0.05 F001 110
778C Thermal Protection 1 Trip Time Constant 0 to 1000 min. 1 F001 45
778D Thermal Protection 1 Reset Time Constant 0 to 1000 min. 1 F001 45
778E Thermal Protection 1 Minimum Reset Time 0 to 1000 min. 1 F001 20
778F Thermal Protection 1 Reset 0 to 4294967295 --- 1 F300 0
7791 Thermal Protection 1 Block 0 to 4294967295 --- 1 F300 0
7793 Thermal Protection 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
Table B–10: MODBUS MEMORY MAP (Sheet 30 of 60)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT