EasyManua.ls Logo

GE B30 UR Series

GE B30 UR Series
582 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Multilin B30 Bus Differential System B-49
APPENDIX B B.4 MEMORY MAPPING
B
AB09 Operand for IEC 61850 XCBR4.ST.Loc Status 0 to 65535 --- 1 F300 0
AB0B Command to Clear XCBR4 OpCnt (Operation
Counter)
0 to 1 --- 1 F126 0 (No)
AB0C Operand for IEC 61850 XCBR5.ST.Loc Status 0 to 65535 --- 1 F300 0
AB0E Command to Clear XCBR5 OpCnt (Operation
Counter)
0 to 1 --- 1 F126 0 (No)
AB0F Operand for IEC 61850 XCBR6.ST.Loc Status 0 to 65535 --- 1 F300 0
AB11 Command to Clear XCBR6 OpCnt (Operation
Counter)
0 to 1 --- 1 F126 0 (No)
IEC 61850 LN Name Prefixes (Read/Write Settings)
AB30 IEC 61850 Logical Node LPHD1 Name Prefix 0 to 65534 --- 1 F206 (none)
AB33 IEC 61850 Logical Node PIOCx Name Prefix (72
items)
0 to 65534 --- 1 F206 (none)
AC0B IEC 61850 Logical Node PTOCx Name Prefix (24
items)
0 to 65534 --- 1 F206 (none)
AC53 IEC 61850 Logical Node PTUVx Name Prefix (13
items)
0 to 65534 --- 1 F206 (none)
AC7A IEC 61850 Logical Node PTOVx Name Prefix (10
items)
0 to 65534 --- 1 F206 (none)
AC98 IEC 61850 Logical Node PDISx Name Prefix (10
items)
0 to 65534 --- 1 F206 (none)
ACB6 IEC 61850 Logical Node RBRFx Name Prefix (24
items)
0 to 65534 --- 1 F206 (none)
ACFE IEC 61850 Logical Node RPSBx Name Prefix 0 to 65534 --- 1 F206 (none)
AD01 IEC 61850 Logical Node RRECx Name Prefix (6
items)
0 to 65534 --- 1 F206 (none)
AD13 IEC 61850 Logical Node MMXUx Name Prefix (6
items)
0 to 65534 --- 1 F206 (none)
AD25 IEC 61850 Logical Node GGIOx Name Prefix (5
items)
0 to 65534 --- 1 F206 (none)
AD34 IEC 61850 Logical Node RFLOx Name Prefix (5
items)
0 to 65534 --- 1 F206 (none)
AD43 IEC 61850 Logical Node XCBRx Name Prefix (6
items)
0 to 65534 --- 1 F206 (none)
AD55 IEC 61850 Logical Node PTRCx Name Prefix (6
items)
0 to 65534 --- 1 F206 (none)
AD67 IEC 61850 Logical Node PDIFx Name Prefix (4
items)
0 to 65534 --- 1 F206 (none)
AD73 IEC 61850 Logical Node MMXNx Name Prefix (37
items)
0 to 65534 --- 1 F206 (none)
ADE2 IEC 61850 Logical Node CSWIx Name Prefix (30
items)
0 to 65534 --- 1 F206 (none)
AE3C IEC 61850 Logical Node XSWIx Name Prefix (24
items)
0 to 65534 --- 1 F206 (none)
IEC 61850 GGIO4 General Analog Configuration Settings (Read/Write Setting)
AF00 Number of Analog Input Points in GGIO4 4 to 32 --- 4 F001 4
IEC 61850 GGIO4 Analog Input Points Configuration Settings (Read/Write Setting) (32 modules)
AF10 IEC 61850 GGIO4 Analog Input 1 Value --- --- --- F600 0
AF11 IEC 61850 GGIO4 Analog Input 1 Deadband 0.001 to 100 % 0.001 F003 100000
AF13 IEC 61850 GGIO4 Analog Input 1 Minimum –1000000000000 to
1000000000000
--- 0.001 F060 0
AF15 IEC 61850 GGIO4 Analog Input 1 Maximum –1000000000000 to
1000000000000
--- 0.001 F060 1000000
AF17 ...Repeated for IEC 61850 GGIO4 Analog Input 2
AF1E ...Repeated for IEC 61850 GGIO4 Analog Input 3
AF25 ...Repeated for IEC 61850 GGIO4 Analog Input 4
AF2C ...Repeated for IEC 61850 GGIO4 Analog Input 5
Table B–10: MODBUS MEMORY MAP (Sheet 41 of 60)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents

Related product manuals