GE Multilin B30 Bus Differential System B-53
APPENDIX B B.4 MEMORY MAPPING
B
IEC 61850 XSWI Configuration (Read/Write Command) (24 modules)
B372 Command to Clear XSWI OpCnt (Operation
Counter)
0 to 1 --- 1 F126 0 (No)
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B400 Number of Status Indications in GGIO1 8 to 128 --- 8 F001 8
B402 IEC 61850 GGIO1 Indication FlexLogic operands
(128 items)
0 to 4294967295 --- 1 F300 0
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0 IEC 61850 Configurable GOOSE Function
(GoEna)
0 to 1 --- 1 F102 1 (Enabled)
B5A1 IEC 61850 Configurable GOOSE ID --- --- --- F209 “GOOSEOut_
x_”
B5C2 Configurable GOOSE Destination MAC Address --- --- --- F072 0
B5C5 IEC 61850 Configurable GOOSE VLAN Transmit
Priority
0 to 7 --- 1 F001 4
B5C6 IEC 61850 Configurable GOOSE VLAN ID 0 to 4095 --- 1 F001 0
B5C7 IEC 61850 Configurable GOOSE ETYPE APPID 0 to 16383 --- 1 F001 0
B5C8 IEC 61850 Configurable GOOSE ConfRev
(Configuration Revision)
1 to 4294967295 --- 1 F003 1
B5CA IEC 61850 Configurable GOOSE Retransmission
Curve
0 to 3 --- 1 F611 3 (Relaxed)
B5CB Configurable GOOSE Dataset Items for
Transmission
(64 items)
0 to 1008 --- 1 F616 0 (None)
B60B ...Repeated for module number 2
B676 ...Repeated for module number 3
B6E1 ...Repeated for module number 4
B74C ...Repeated for module number 5
B7B7 ...Repeated for module number 6
B822 ...Repeated for module number 7
B88D ...Repeated for module number 8
IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (16 modules)
B900 Configurable GOOSE Dataset Items for Reception
(32 items)
0 to 197 --- 1 F233 0 (None)
B920 ...Repeated for module number 2
B940 ...Repeated for module number 3
B960 ...Repeated for module number 4
B980 ...Repeated for module number 5
B9A0 ...Repeated for module number 6
B9C0 ...Repeated for module number 7
B9E0 ...Repeated for module number 8
BA00 ...Repeated for module number 9
BA20 ...Repeated for module number 10
BA40 ...Repeated for module number 11
BA60 ...Repeated for module number 12
BA80 ...Repeated for module number 13
BAA0 ...Repeated for module number 14
BAC0 ...Repeated for module number 15
BAE0 ...Repeated for module number 16
Contact Inputs (Read/Write Setting) (96 modules)
BB00 Contact Input 1 Name --- --- --- F205 “Cont Ip 1“
BB06 Contact Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
BB07 Contact Input 1 Debounce Time 0 to 16 ms 0.5 F001 20
Table B–10: MODBUS MEMORY MAP (Sheet 45 of 60)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT