5-68 B30 Bus Differential System GE Multilin
5.2 PRODUCT SETUP 5 SETTINGS
5
c) SNTP PROTOCOL
PATH: SETTINGS PRODUCT SETUP  REAL TIME CLOCK  SNTP PROTOCOL
The B30 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the B30 can obtain clock time
over an Ethernet network. The B30 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded-
icated product using a GPS receiver to provide an accurate time. UR series relays support unicast, broadcast, multicast,
and anycast SNTP functionality.
The
SNTP FUNCTION setting enables or disabled the SNTP feature on the B30.
To use SNTP in unicast mode,
SNTP SERVER IP ADDR must be set to the SNTP/NTP server IP address. Once this address is
set and
SNTP FUNCTION is “Enabled,” the B30 attempts to obtain time values from the SNTP/NTP server. Since many time
values are obtained and averaged, it generally takes three to four minutes until the B30 clock is closely synchronized with
the SNTP/NTP server. It takes up to two minutes for the B30 to signal an SNTP self-test error if the server is offline.
To use SNTP in broadcast mode, set the SNTP SERVER IP ADDR setting to “0.0.0.0” and SNTP FUNCTION to “Enabled.” The
B30 then listens to SNTP messages sent to the “all ones” broadcast address for the subnet. The B30 waits up to 18 min-
utes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error.
The SNTP UDP PORT NUMBER is 123 for normal SNTP operation. If SNTP is not required, close the port by setting it to 0.
When the SNTP UDP PORT NUMBER is set to 0, the change takes effect when the B30 is restarted.
d) LOCAL TIME
PATH: SETTINGS PRODUCT SETUP  REAL TIME CLOCK  LOCAL TIME
SNTP PROTOCOL
SNTP FUNCTION:
Disabled
Range: Enabled, Disabled
MESSAGE
SNTP SERVER IP ADDR:
0.0.0.0
Range: Standard IP address format
MESSAGE
SNTP UDP PORT
NUMBER: 123
Range: 0 to 65535 in steps of 1
LOCAL TIME
LOCAL TIME OFFSET
FROM UTC: 0.0 hrs
Range: –24.0 to 24.0 hrs in steps of 0.5
MESSAGE
DAYLIGHT SAVINGS
TIME: Disabled
Range: Disabled, Enabled
MESSAGE
DST START MONTH:
January
Range: January to December (all months)
MESSAGE
DST START DAY:
Sunday
Range: Sunday to Saturday (all days of the week)
MESSAGE
DST START DAY
INSTANCE: First
Range: First, Second, Third, Fourth, Last
MESSAGE
DST START HOUR:
2
Range: 0 to 23
MESSAGE
DST STOP MONTH:
January
Range: January to December (all months)
MESSAGE
DST STOP DAY:
Sunday
Range: Sunday to Saturday (all days of the week)
MESSAGE
DST STOP DAY
INSTANCE: First
Range: First, Second, Third, Fourth, Last
MESSAGE
DST STOP HOUR:
2
Range: 0 to 23
NOTE

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)

Related product manuals