GE Multilin B30 Bus Differential System B-13
APPENDIX B B.4 MEMORY MAPPING
B
06E4 ...Repeated for Binary Input 89
06E8 ...Repeated for Binary Input 90
06EC ...Repeated for Binary Input 91
06F0 ...Repeated for Binary Input 92
06F4 ...Repeated for Binary Input 93
06F8 ...Repeated for Binary Input 94
06FC ...Repeated for Binary Input 95
0700 ...Repeated for Binary Input 96
IEC 103 ASDU Settings (Read/Write Setting) (4 modules)
0704 IEC103 ASDU1 TYP 0 to 1 --- 1 F630 1(9)
0705 IEC103 ASDU 1 FUN 0 to 255 --- 1 F001 0
0706 IEC103 ASDU 1 INF 0 to 255 --- 1 F001 0
0707 IEC103 ASDU 1 Scan Timeout 0 to 1000 --- 1 F001 0
0708 IEC103 ASDU 1 Analog Param 1 0 to 65535 --- 1 F600 0
0709 IEC103 ASDU 1 Analog Factor 1 0 to 65.535 --- 0.001 F001 1000
070A IEC103 ASDU 1 Analog Offset 1 -32768 to 32767 --- 1 F002 0
070B IEC103 ASDU 1 Analog Param 2 0 to 65535 --- 1 F600 0
070C IEC103 ASDU 1 Analog Factor 2 0 to 65.535 --- 0.001 F001 1000
070D IEC103 ASDU 1 Analog Offset 2 -32768 to 32767 --- 1 F002 0
070E IEC103 ASDU 1 Analog Param 3 0 to 65535 --- 1 F600 0
070F IEC103 ASDU 1 Analog Factor 3 0 to 65.535 --- 0.001 F001 1000
0710 IEC103 ASDU 1 Analog Offset 3 -32768 to 32767 --- 1 F002 0
0711 IEC103 ASDU 1 Analog Param 4 0 to 65535 --- 1 F600 0
0712 IEC103 ASDU 1 Analog Factor 4 0 to 65.535 --- 0.001 F001 1000
0713 IEC103 ASDU 1 Analog Offset 4 -32768 to 32767 --- 1 F002 0
0714 IEC103 ASDU 1 Analog Param 5 0 to 65535 --- 1 F600 0
0715 IEC103 ASDU 1 Analog Factor 5 0 to 65.535 --- 0.001 F001 1000
0716 IEC103 ASDU 1 Analog Offset 5 -32768 to 32767 --- 1 F002 0
0717 IEC103 ASDU 1 Analog Param 6 0 to 65535 --- 1 F600 0
0718 IEC103 ASDU 1 Analog Factor 6 0 to 65.535 --- 0.001 F001 1000
0719 IEC103 ASDU 1 Analog Offset 6 -32768 to 32767 --- 1 F002 0
071A IEC103 ASDU 1 Analog Param 7 0 to 65535 --- 1 F600 0
071B IEC103 ASDU 1 Analog Factor 7 0 to 65.535 --- 0.001 F001 1000
071C IEC103 ASDU 1 Analog Offset 7 -32768 to 32767 --- 1 F002 0
071D IEC103 ASDU 1 Analog Param 8 0 to 65535 --- 1 F600 0
071E IEC103 ASDU 1 Analog Factor 8 0 to 65.535 --- 0.001 F001 1000
071F IEC103 ASDU 1 Analog Offset 8 -32768 to 32767 --- 1 F002 0
0720 IEC103 ASDU 1 Analog Param 9 0 to 65535 --- 1 F600 0
0721 IEC103 ASDU 1 Analog Factor 9 0 to 65.535 --- 0.001 F001 1000
0722 IEC103 ASDU 1 Analog Offset 9 -32768 to 32767 --- 1 F002 0
0723 ...Repeated for IEC103 ASDU 2
0742 ...Repeated for IEC103 ASDU 3
0761 ...Repeated for IEC103 ASDU 4
IEC 103 Commands (Read/Write Setting) (32 modules)
0780 IEC103 Command 1 FUN 0 to 255 --- 1 F001 0
0781 IEC103 Command 1 INF 0 to 255 --- 1 F001 0
0782 IEC103 Command 1 Param ON 0 to 64 --- 1 F631 0 (OFF)
0783 IEC103 Command 1 Param OFF 0 to 64 --- 1 F631 0 (OFF)
0784 ...Repeated for IEC103 Command 2
Table B–10: MODBUS MEMORY MAP (Sheet 5 of 64)