GE Multilin B30 Bus Differential System B-15
APPENDIX B B.4 MEMORY MAPPING
B
User Displays Actuals (Read Only)
1080 Formatted user-definable displays (16 items) --- --- --- F200 (none)
Modbus User Map Actuals (Read Only)
1200 User Map Values (256 items) 0 to 65535 --- 1 F001 0
Element Targets (Read Only)
14E0 Target Sequence 0 to 65535 --- 1 F001 0
14E1 Number of Targets 0 to 65535 --- 1 F001 0
Element Targets (Read/Write)
14E2 Target to Read 0 to 65535 --- 1 F001 0
Element Targets (Read Only)
14E3 Target Message --- --- --- F200 “.”
Contact Input/Output States (Read Only)
1500 Contact Input States (6 items) 0 to 65535 --- 1 F500 0
1508 Virtual Input States (8 items) 0 to 65535 --- 1 F500 0
1510 Contact Output States (4 items) 0 to 65535 --- 1 F500 0
1518 Contact Output Current States (4 items) 0 to 65535 --- 1 F500 0
1520 Contact Output Voltage States (4 items) 0 to 65535 --- 1 F500 0
1528 Virtual Output States (6 items) 0 to 65535 --- 1 F500 0
1530 Contact Output Detectors (4 items) 0 to 65535 --- 1 F500 0
Remote Input/Output States (Read Only)
1540 Remote Device States (2 items) 0 to 65535 --- 1 F500 0
1542 Remote Input States (4 items) 0 to 65535 --- 1 F500 0
1550 Remote Devices Online 0 to 1 --- 1 F126 0 (No)
1551 Remote Double-Point Status Input 1 State 0 to 3 --- 1 F605 3 (Bad)
1552 Remote Double-Point Status Input 2 State 0 to 3 --- 1 F605 3 (Bad)
1553 Remote Double-Point Status Input 3 State 0 to 3 --- 1 F605 3 (Bad)
1554 Remote Double-Point Status Input 4 State 0 to 3 --- 1 F605 3 (Bad)
1555 Remote Double-Point Status Input 5 State 0 to 3 --- 1 F605 3 (Bad)
Platform Direct Input/Output States (Read Only)
15C0 Direct Input States (6 items) 0 to 65535 --- 1 F500 0
15C8 Direct Outputs Average Message Return Time 1 0 to 65535 ms 1 F001 0
15C9 Direct Outputs Average Message Return Time 2 0 to 65535 ms 1 F001 0
15CA Direct Inputs/Outputs Unreturned Message Count -
Ch. 1
0 to 65535 --- 1 F001 0
15CB Direct Inputs/Outputs Unreturned Message Count -
Ch. 2
0 to 65535 --- 1 F001 0
15D0 Direct Device States 0 to 65535 --- 1 F500 0
15D1 Reserved 0 to 65535 --- 1 F001 0
15D2 Direct Inputs/Outputs CRC Fail Count 1 0 to 65535 --- 1 F001 0
15D3 Direct Inputs/Outputs CRC Fail Count 2 0 to 65535 --- 1 F001 0
Field Unit Input/Output States (Read Only)
15E0 Field Unit Contact Input States (3 items) 0 to 65535 --- 1 F500 0
15E3 Field Unit Contact Input Output Operand States (8
items)
0 to 65535 --- 1 F500 0
15EB Field Contact Output Physical States (8 items) 0 to 65535 --- 1 F500 0
15F3 Field Contact Output Current States (8 items) 0 to 65535 --- 1 F500 0
15FB Field Contact Output Physical States (8 items) 0 to 65535 --- 1 F500 0
1603 Field Shared Input States 0 to 65535 --- 1 F500 0
1604 Field Shared Input Channel States 0 to 65535 --- 1 F500 0
1605 Field Shared Input Test States 0 to 65535 --- 1 F500 0
Table B–10: MODBUS MEMORY MAP (Sheet 7 of 64)