B-56 B30 Bus Differential System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
IEC 61850 XSWI Configuration (Read/Write Setting) (24 modules)
B370 FlexLogic Operand for IEC 61850 XSWI.ST.Loc
Status
0 to 4294967295 --- 1 F300 0
B373 ...Repeated for module number 2
B376 ...Repeated for module number 3
B379 ...Repeated for module number 4
B37C ...Repeated for module number 5
B37F ...Repeated for module number 6
B382 ...Repeated for module number 7
B385 ...Repeated for module number 8
B388 ...Repeated for module number 9
B38B ...Repeated for module number 10
B38E ...Repeated for module number 11
B391 ...Repeated for module number 12
B394 ...Repeated for module number 13
B397 ...Repeated for module number 14
B39A ...Repeated for module number 15
B39D ...Repeated for module number 16
B3A0 ...Repeated for module number 17
B3A3 ...Repeated for module number 18
B3A6 ...Repeated for module number 19
B3A9 ...Repeated for module number 20
B3AC ...Repeated for module number 21
B3AF ...Repeated for module number 22
B3B2 ...Repeated for module number 23
B3B5 ...Repeated for module number 24
IEC 61850 XSWI Configuration (Read/Write Command) (24 modules)
B372 Command to Clear XSWI OpCnt (Operation
Counter)
0 to 1 --- 1 F126 0 (No)
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B400 Number of Status Indications in GGIO1 8 to 128 --- 8 F001 8
B402 IEC 61850 GGIO1 Indication FlexLogic operands
(128 items)
0 to 4294967295 --- 1 F300 0
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0 IEC 61850 Configurable GOOSE Function
(GoEna)
0 to 1 --- 1 F102 1 (Enabled)
B5A1 IEC 61850 Configurable GOOSE ID --- --- --- F209 “GOOSEOut_
x_”
B5C2 Configurable GOOSE Destination MAC Address --- --- --- F072 0
B5C5 IEC 61850 Configurable GOOSE VLAN Transmit
Priority
0 to 7 --- 1 F001 4
B5C6 IEC 61850 Configurable GOOSE VLAN ID 0 to 4095 --- 1 F001 0
B5C7 IEC 61850 Configurable GOOSE ETYPE APPID 0 to 16383 --- 1 F001 0
B5C8 IEC 61850 Configurable GOOSE ConfRev
(Configuration Revision)
1 to 4294967295 --- 1 F003 1
B5CA IEC 61850 Configurable GOOSE Retransmission
Curve
0 to 3 --- 1 F611 3 (Relaxed)
B5CB Configurable GOOSE Dataset Items for
Transmission
(64 items)
0 to 1008 --- 1 F616 0 (None)
B60B ...Repeated for module number 2
B676 ...Repeated for module number 3
B6E1 ...Repeated for module number 4
Table B–10: MODBUS MEMORY MAP (Sheet 48 of 64)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents