5-190 C60 Breaker Protection System GE Multilin
5.6 GROUPED ELEMENTS 5 SETTINGS
5
Figure 5–76: SINGLE-POLE BREAKER FAILURE, TIMERS
Initiated phase A
from single-pole breaker
failure logic sheet 1
Use Timer 2
SETTING
Yes = 1
No = 0
827070A5.CDR
IB
IC
Use Timer 1
SETTINGS
No = 0
Yes = 1
Breaker Pos 1 Phase A/3P
Off = 0
SETTINGS
Breaker Pos 1 Phase B
Off = 0
Initiated phase B
from single-pole breaker
failure logic sheet 1
0
Timer 1 Pickup Delay
SETTING
AND
0
Timer 2 Pickup Delay
SETTING
AND
0
Timer 1 Pickup Delay
SETTING
AND
0
Timer 2 Pickup Delay
SETTING
AND
SETTINGS
Breaker Pos 1 Phase B
Off = 0
0
Timer 1 Pickup Delay
SETTING
AND
Initiated phase C
from single-pole breaker
failure logic sheet 1
0
Timer 2 Pickup Delay
SETTING
AND
Use Timer 3
SETTINGS
Yes = 1
Breaker Pos 2 Phase A/3P
Off = 0
Breaker Pos 2 Phase B
Off = 0
Breaker Pos 2 Phase C
Off = 0
Breaker Test On
Off = 0
AND
Initiated
from single-pole breaker failure logic sheet 1
0
Timer 3 Pickup Delay
SETTING
AND
AND
OR
AND
OR
OR
SETTING
Phase Current HiSet Pickup
RUN
IA
0
LoSet Time Delay
SETTING
SETTING
Phase Current HiSet Pickup
RUN
0
LoSet Time Delay
SETTING
Pickup
IB
Pickup
SETTING
Phase Current HiSet Pickup
RUN
0
LoSet Time Delay
SETTING
IC Pickup
SETTING
Phase Current LoSet Pickup
RUN
IA Pickup
SETTING
Phase Current LoSet Pickup
RUN
IB Pickup
SETTING
Phase Current LoSet Pickup
RUN
IC Pickup
OR
OR
OR
0
Trip Dropout Delay
SETTING
FLEXLOGIC OPERAND
BKR FAIL 1 TRIP OP
FLEXLOGIC OPERAND
BKR FAIL 1 T3 OP
FLEXLOGIC OPERAND
BKR FAIL 1 T2 OP
FLEXLOGIC OPERAND
BKR FAIL 1 T1 OP
IA