A-8 C60 Breaker Protection System GE Multilin
A.1 PARAMETER LISTS APPENDIX A
A
7734 SRC 4 Demand Watt Watts Source 4 real power demand
7736 SRC 4 Demand var Vars Source 4 reactive power demand
7738 SRC 4 Demand Va VA Source 4 apparent power demand
8672 Brk 1 Arc Amp A
kA
2
-cyc
Breaker 1 arcing amp phase A
8674 Brk 1 Arc Amp B
kA
2
-cyc
Breaker 1 arcing amp phase B
8676 Brk 1 Arc Amp C
kA
2
-cyc
Breaker 1 arcing amp phase C
8678 Brk 1 Op Time A ms Breaker 1 operating time phase A
8679 Brk 1 Op Time B ms Breaker 1 operating time phase B
8680 Brk 1 Op Time C ms Breaker 1 operating time phase C
8681 Brk 1 Op Time ms Breaker 1 operating time
8682 Brk 2 Arc Amp A
kA
2
-cyc
Breaker 2 arcing amp phase A
8684 Brk 2 Arc Amp B
kA
2
-cyc
Breaker 2 arcing amp phase B
8686 Brk 2 Arc Amp C
kA
2
-cyc
Breaker 2 arcing amp phase C
8688 Brk 2 Op Time A ms Breaker 2 operating time phase A
8689 Brk 2 Op Time B ms Breaker 2 operating time phase B
8690 Brk 2 Op Time C ms Breaker 2 operating time phase C
8691 Brk 2 Op Time ms Breaker 2 operating time
9024 Prefault Ia Mag [1] Amps Fault 1 pre-fault phase A current magnitude
9026 Prefault Ia Ang [1] Degrees Fault 1 pre-fault phase A current angle
9027 Prefault Ib Mag [1] Amps Fault 1 pre-fault phase B current magnitude
9029 Prefault Ib Ang [1] Degrees Fault 1 pre-fault phase B current angle
9030 Prefault Ic Mag [1] Amps Fault 1 pre-fault phase C current magnitude
9032 Prefault Ic Ang [1] Degrees Fault 1 pre-fault phase C current angle
9033 Prefault Va Mag [1] Volts Fault 1 pre-fault phase A voltage magnitude
9035 Prefault Va Ang [1] Degrees Fault 1 pre-fault phase A voltage angle
9036 Prefault Vb Mag [1] Volts Fault 1 pre-fault phase B voltage magnitude
9038 Prefault Vb Ang [1] Degrees Fault 1 pre-fault phase B voltage angle
9039 Prefault Vc Mag [1] Volts Fault 1 pre-fault phase C voltage magnitude
9041 Prefault Vc Ang [1] Degrees Fault 1 pre-fault phase C voltage angle
9042 Fault Ia Mag [1] Amps Fault 1 phase A current magnitude
9044 Fault Ia Ang [1] Degrees Fault 1 phase A current angle
9045 Fault Ib Mag [1] Amps Fault 1 phase B current magnitude
9047 Fault Ib Ang [1] Degrees Fault 1 phase B current angle
9048 Fault Ic Mag [1] Amps Fault 1 phase C current magnitude
9050 Fault Ic Ang [1] Degrees Fault 1 phase C current angle
9051 Fault Va Mag [1] Volts Fault 1 phase A voltage magnitude
9053 Fault Va Ang [1] Degrees Fault 1 phase A voltage angle
9054 Fault Vb Mag [1] Volts Fault 1 phase B voltage magnitude
9056 Fault Vb Ang [1] Degrees Fault 1 phase B voltage angle
9057 Fault Vc Mag [1] Volts Fault 1 phase C voltage magnitude
9059 Fault Vc Ang [1] Degrees Fault 1 phase C voltage angle
9060 Fault Type [1] --- Fault 1 type
9061 Fault Location [1] --- Fault 1 location
9216 Synchchk 1 Delta V Volts Synchrocheck 1 delta voltage
9218 Synchchk 1 Delta F Hz Synchrocheck 1 delta frequency
9219 Synchchk 1 Delta Phs Degrees Synchrocheck 1 delta phase
Table A–1: FLEXANALOG DATA ITEMS (Sheet 8 of 13)
ADDRESS FLEXANALOG NAME UNITS DESCRIPTION